background image

7

 ATTENTION – 

A

Refer to document “String inverters - Product 

manual appendix” available at 

www.fimer.com

 to find out the 

manufacturer and model of quick fit connector used on the inverter.

Click 

Click 

 ATTENTION – 

A

Check that protective caps are installed on unused 

connectors. This is necessary for the inverter seal and to avoid any 

damage to the unused connectors which may be used at a later time.

 ATTENTION – 

A

The quick fit connectors must be properly installed. 

After the installation make sure the connectors are correctly locked 

through the clips. 

9.  Instruments

The synoptic 

(03)

 allows to view inverter status conditions to be analyzed 

in greater depth by consulting the manual.

POWER

Solid when the inverter is working correctly. Flashes when 

checking the grid or if there is insufficient sunlight.

WLAN

Indicates the status of the Wi-Fi or Ethernet communication lines.

ALARM

The inverter has detected an anomaly. The anomaly is shown 

on the “EVENTS” section of the internal webserver.

GFI

Ground fault on the DC side of the PV generator. The error 

is shown on the “EVENTS” section of the internal webserver. 

 NOTE – 

D

The icons, in various combinations, can indicate multiple 

conditions other than the original single condition; see the various 

descriptions on the product manual.

10.  Commissioning

The inverter can be commissioned in a simple and intuitive way through 

the Installer for solar inverters APP for mobile devices.

 NOTE – 

D

The same configurations can be done via internal web 

User Interface (see product manual).

• Supply the inverter with DC input voltage from the photovoltaic generator 

and via AC grid voltage.

 ATTENTION – 

A

The inverter configuration can be also performed 

with only one supply source (DC or AC). 

 ATTENTION – 

A

With DC supply, make sure that the irradiation is 

stable and adequate for the inverter commissioning procedure to be 

completed.

• Open the " Installer for solar inverters" APP.

• Login or Sign-In to Aurora vision account.

• Tap on "Commissioning wizard". A QR code scanner will be opened.

• Scan the QR code on the 

Communication identification label and 

connect to inverter network.

 NOTE – 

D

The name of the Wi-Fi 

network created by the inverter will 

be: FIMER-YYWWSSSSSS (10 

digit Inverter SN).

 NOTE – 

D

After this step wait 10 seconds to allow the Wi-Fi connection

Once connected, the commissioning wizard will start.

10.1  COMMISSIONING WIZARD

10.1.1  Network configuration.

• Choose the connection type (ethernet or wireless) and set the related 

parameters.

 NOTE – 

D

This step can be skipped and performed later (via WebUI).

• Once network parameters were setted, tap on “Next”.

10.1.2  Date and Time.

• Set the Date, Time and Time zone 

(The inverter will propose these fields if 

connected to internet).

• Once date and time were setted, tap on 

“Next”.

10.1.3  Inverter configuration.

Country standard

• Set the grid standard of the country 

in which the inverter is installed. 

Some Country standards have different 

grid voltage that should be setted during 

this step.

•   Confirm the settings by clicking “Save”. 

The configuration wizard is complete 

and the inverter will reboot.

• If the outcome of the preliminary checks on the grid parallel is positive, the 

inverter connects to the grid and starts to export power to the grid. The 

“Power” LED remains fixed on while the “Alarm” and “GFI” LEDs are off.

 NOTE – 

D

To address any problems that may occur during the 

initial stages of operation of the system and to ensure the inverter 

remains fully functional, you are advised to check for any firmware 

updates in the download area of the website www.fimer.com or at 

https://registration.solar.fimer.com (instructions for registering on the 

website and updating the firmware are given in the product manual).

WLAN MAC: XX:XX:XX:XX:XX:XX

Remove and apply 

on the Quick

Installation Guide

ETH1 MAC: XX:XX:XX:XX:XX:XX

ETH2 MAC: XX:XX:XX:XX:XX:XX

SN Inverter: YYWWSSSSSS
PK: 0000-0000-0000-0000

1.

Содержание PVS-10-TL

Страница 1: ...tion information provided in the product manual must be read and followed The technical documentation for the product is available at the website The device must be used in the manner described in the manual If this is not the case the safety devices guaranteed by the inverter might be ineffective APPLY HERE THE COMMUNICATION IDENTIFICATION LABEL ...

Страница 2: ...who has a good knowledge of the installation conditions the devices that will be installed externally and whether it will eventually be integrated into an existing system 1 1 Main inverter components Inverter external view 01 Inverter 10 USB connector for accessories board 18 Side bracket screws 02 Heatsink 11 Ethernet 1 2 connectors 19 Padlock hole 03 Synoptic LED icons 12 Digital input and RS485...

Страница 3: ...g and transporting Transportation and relocation The transportation of the device in particular via land transportation must be made with adequate means and ways to protect the parts from violent impacts humidity vibrations etc ATTENTION A If the package is stored correctly it can withstand a maximum load of 5 stacked pallet 2 units each pallet Lifting The means used for lifting must be suitable t...

Страница 4: ...clearance distances H of 100cm 39 and I of 30cm 12 G I I H H H G G ATTENTION A Please check the product manual for Wireless signal environmental checks Installations at high altitudes and Installations with a high level of humidity NOTE D The final installation of the inverter must not compromise the access to any disconnection devices located outside NOTE D Refer to the warranty conditions to eva...

Страница 5: ...g the specific AC quick fit connector 09 supplied AC conductor cable Cable diameter range 11 19 mm or 19 26mm based on the type of seals installed Conductor cross section 6mm2 16mm2 with plastic collar ferrule accepted by the AC quick fit connector Conductor material copper 7 3 Protection switch under load AC switch and differential protection To protect the AC connection line of the inverter it i...

Страница 6: ...o not connect weights to the AC cable do not leave excess cable windings hanging etc 8 Input connection DC For the strings connections it is necessary to use the DC input quick fit connectors 13 located on the bottom side of the inverter 13 The input connectors are divided into 2 groups one group for each input MPPT For each MPPT 2 pairs of quick fit connectors are available Respect the Maximum DC...

Страница 7: ...ioning procedure to be completed Open the Installer for solar inverters APP Login or Sign In to Aurora vision account Tap on Commissioning wizard A QR code scanner will be opened Scan the QR code on the Communication identification label and connect to inverter network NOTE D The name of the Wi Fi network created by the inverter will be FIMER YYWWSSSSSS 10 digit Inverter SN NOTE D After this step ...

Страница 8: ... A 32 A 32 A Output overvoltage protection SPD Type 2 Operating performance Maximum Efficiency ηmax 98 4 98 5 98 5 Weighted Efficiency EURO 98 1 98 2 98 2 Environmental Operating ambient temperature range 25 60 C 13 140 F with derating above 45 C 113 F Storage temperature 40 C 85 C 40 F 185 F Relative Humidity 4 100 with condensation Sound pressure level typical 40 dB A 1m 45 dB A 1m 45 dB A 1m Ma...

Отзывы: