background image

 

 The detector will automatically enable the signal processing after 10 min-
utes.

 

 T

esting the detector will activate the alarm relay and send a signal to 

the panel.

CLEANING

Before removing the detector, notify the proper authorities that the smoke 
detector system is undergoing maintenance and will be temporarily out of 
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.
1.  Remove the sensor to be cleaned from the system.
2.   Remove the sensor cover by pressing firmly on each of the four removal 

tabs that hold the cover in place. (See Figure 4.) 

3.   Vacuum the screen carefully without removing it. If further cleaning is 

required continue with Step 4, otherwise skip to Step 7.

4.   Remove the chamber cover/screen assembly by pulling it straight out.
5.   Use a vacuum cleaner or compressed air to remove dust and debris from 

the sensing chamber.

6.   Reinstall the chamber cover/screen assembly by aligning the arrows on 

the top with the two round-top posts on the sensing chamber, and gently 
pressing it until it fits securely. 

7.   Replace the cover using the LEDs to align the cover and then gently push-

ing it until it locks into place. NOTE: Make sure that the thermistors do not 
become bent under the cover. 

8.  Reinstall the detector.
9.  Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.

ABOUT CARBON MONOXIDE DETECTORS 

CAUTION

 

CAUTION: This carbon monoxide detector is designed for indoor use only. 
Do not expose to rain or moisture. Do not knock or drop the detector. The 
detector will not protect against the risk of carbon monoxide poisoning if 
not properly wired. The detector will only indicate the presence of carbon 
monoxide gas at the sensor. Carbon monoxide gas may be present in other 
areas.

This carbon monoxide detector is NOT:

•  Designed to detect any gas other than carbon monoxide
•  To be seen as a substitute for the proper servicing of fuel-burning appli-

ances or the sweeping of chimneys.

•  To be used on an intermittent basis, or as a portable alarm for the spill-

age of combustion products from fuel-burning appliances or chimneys.

Carbon monoxide gas is a highly poisonous gas which is released when fuels 
are burnt. It is invisible, has no smell and is therefore impossible to detect 
with the human senses. Under normal conditions in a room where fuel burn-
ing appliances are well maintained and correctly ventilated, the amount of 
carbon monoxide released into the room by appliances should not be danger-
ous.

SYMPTOMS OF CARBON MONOXIDE POISONING

Carbon monoxide bonds to the hemoglobin in the blood and reduces the 
amount of oxygen being circulated in the body. The following symptoms are 
examples taken from NFPA 72 and 720. They represent approximate values 
for healthy adults: 

Concentration (ppm CO)

Symptoms

200

Mild headache  

after 2-3 hours of exposure

400

Headache and nausea  

after 1-2 hours of exposure

800

Headache, nausea, and dizziness  

after 45 minutes of exposure;  

collapse and unconsciousness  

after 2 hours of exposure

Many causes of reported carbon monoxide poisoning indicate that while vic-
tims are aware that they are not well, they become so disoriented that they 
are unable to save themselves by either exiting the building or calling for 
assistance. 
Also young children and pets may be the first to be affected.
Per UL standard 2075, FIK-PC351 has been tested to the sensitivity limits de-
fined in UL standard 2034. 

ALARM THRESHOLDS ARE AS FOLLOWS: 

Parts Per Million

Detector response time, min.

70 ±5ppm

60-240

150 ±5ppm

10-50

400 ±10ppm

4-15

What to do if the carbon monoxide detector goes into alarm: 
Immediately move to a spot where fresh air is available, preferably out-
doors. 
IMPORTANT: This detector should be tested and maintained regularly fol-
lowing National Fire Protection Association (NFPA) 72 and 720 require-
ments. 

CO SENSOR LIFETIME 

The CO cell has an expected lifetime of approximately ten years. The detector 
is programmed to signal the approach of end of this lifetime to the control 
panel. The CO cell is not a field replaceable component. The smoke sensor 
will continue to operate using the photoelectric sensing element even though 
the CO cell is no longer operational. The CO detector will not operate once the 
CO cell has reached its end of life.

SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS

Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.

  

I56-6638-000 

 

 1/15/2021

Содержание FIK-PC351

Страница 1: ...iance with the control panel system installation manual For local audible indication of a fire and or carbon monoxide alarm it is recommended to install the multi criteria photoelec tric and carbon monoxide CO sensor into a B200S series sounder base If a local audible device is not used care should be taken to develop a proper response plan The installation must meet the requirements of the Author...

Страница 2: ...t The magnet test initiates an approximately 10 minute period when the detec tor s signal processing software routines are not active Once in test mode test the smoke detector using one of the tested and ap proved aerosol smoke products Refer to the manufacturer s published instruc tions for proper use of the canned smoke agent When used properly the canned smoke agent will cause the smoke detecto...

Страница 3: ...s Carbon monoxide gas is a highly poisonous gas which is released when fuels are burnt It is invisible has no smell and is therefore impossible to detect with the human senses Under normal conditions in a room where fuel burn ing appliances are well maintained and correctly ventilated the amount of carbon monoxide released into the room by appliances should not be danger ous SYMPTOMS OF CARBON MON...

Страница 4: ...e and 2 this device must accept any interference received including interference that may cause undesired operation NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates use...

Отзывы: