background image

FIGURE 3. FEATURES OF THE PHOTO/CO DETECTOR

Base Alignment Notch

CO Test Point

Magnet Test Point

LEDs

 C2046-00

FIGURE 4. CLEANING THE PHOTO/CO DETECTOR

Cover 

Removal 

Tabs

Sensor Cover

Sensing Chamber 

Cover and Screen

Sensing 

Chamber 

}

 C2047-00

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction.

TAMPER RESISTANCE

Model FIK-PC351 includes a tamper-resistant capability that prevents removal 
from the base without the use of a tool. Refer to the base manual for details on 
making use of this capability.

TESTING

Before testing, notify the proper authorities that the system is undergoing 
maintenance, and will temporarily be out of service. Disable the system to 
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors 
offer maximum performance when tested and maintained in compliance with 
NFPA 72. Sensitivity readings are available through the FACP. Refer to the 
manufac turer’s published instructions for proper use.
The sensor can be tested in the following ways:

A.  Functional: Magnet Test (P/N M02-04-01 or M02-09-00) 

 

 This sensor can be functionally tested with a test magnet. The test magnet 
electronically simulates smoke in the sensing chamber, testing the sensor 
electronics and connections to the control panel.

 

a.   Hold the test magnet in the magnet test area as shown in Figure 3.

 

b.  The sensor should alarm the panel.

   Two LEDs on the sensor are controlled by the panel to indicate sensor 

status. Coded signals, transmitted from the panel, can cause the LEDs to 
blink, latch on, or latch off. Refer to the control panel technical documen-
tation for sensor LED status operation and expected delay to alarm.

 

 NOTE: The magnet test initiates an approximately 10 minute period when 
the detector's signal processing software routines are not active.

B.  Smoke Entry

 

 Canned aerosol simulated smoke (canned smoke agent) may be used for 
smoke entry testing of the smoke detector. 

   The multi-criteria photoelectric and CO detector uses algorithms to pro-

cess signals received from multiple sensors to determine alarm conditions 
and reduce false alarms. Therefore, a single burst of canned smoke will 
not immediately place the detector into an alarm condition because the 
detector algorithms correctly determine a burst of canned smoke is not 
fire. In order to perform functional testing of the photoelectric sensor, the 
device must be placed into test mode. Test mode allows the detector to 
isolate the individual sensors for testing. The device can be placed into 
test mode through either of the following methods.

   a. Put the device into test mode by holding a test magnet in the magnet 

test area as shown in Figure 3 for 6-12 seconds.

 

 NOTE: If the magnet is held in place for too long the fire alarm test func-
tion will be triggered. (See Magnet Test, above.) Reset the panel and pro-
ceed with testing the smoke entry portion of the device. 

 

 b. Perform smoke entry testing immediately following the magnet test. The 
magnet test initiates an approximately 10 minute period when the detec-
tor’s signal processing software routines are not active.

Once in test mode, test the smoke detector using one of the tested and ap-
proved aerosol smoke products. Refer to the manufacturer’s published instruc-
tions for proper use of the canned smoke agent. When used properly, the 
canned smoke agent will cause the smoke detector to go into alarm.
Tested and approved aerosol smoke products include:

Manufacturer

Model

HSI Fire and Safety 

25S, 30S (PURCHECK)

SDi

SMOKE CENTURION , SOLO A10, 
SMOKESABRE, TRUTEST, SOLO 365

No Climb

TESTIFIRE 2000

CAUTION

Canned aerosol simulated smoke (canned smoke agent) formulas will vary  
by manufacturer. Misuse or overuse of these products may have long term  
adverse effects on the smoke detector. Consult the canned smoke agent manu-
facturer’s published instructions for any further warnings or caution statements.

C.  Multi-Criteria Testing

 

 Testifire® by SDi provides testing of the photoelectric and CO sensors. Consult 
the manufacturer’s published instructions for complete usage instructions.

A sensor that fails any of these tests may need to be cleaned as described 
under CLEANING, and retested. When testing is complete, restore the system 
to normal operation and notify the proper authorities that the system is back 
in operation.

D.  Functional Gas Test

 

 NOTE: Check with local codes and the AHJ to determine whether or not a 
functional gas test is desired for an installation. 

 

 A canned CO testing agent may be used to verify the detector’s ability to 
sense CO. Carbon Monoxide alarm thresholds are designed around CO 
concentrations over time, as defined in UL standard 2034. Therefore, a 
single burst of CO test agent will not immediately place the detector into 
an alarm condition. In order to perform functional testing of the CO sen-
sor, the device must be placed into test mode. Test mode eliminates the 
time and concentration requirements needed for alarm and allows the CO 
sensor to be tested. The device can be placed into test mode through either 
of the following methods.

   a. Put the device into test mode by holding a test magnet in the magnet 

test area as shown in Figure 3 for 6-12 seconds.

 

 NOTE: If the magnet is held in place for too long the fire alarm test func-
tion will be triggered. Reset the panel and proceed with testing the CO 
portion of the device. 

 

 b. Perform functional gas entry testing immediately following the magnet 
test. The magnet test initiates an approximately 10 minute period when 
the detector's signal processing software routines are not active. 

 

 Once in test mode, test the CO sensor using a tested and approved canned 
CO testing agent. A tested and approved canned CO testing agent is Solo 
detector testers model C6 CO Detector Tester available from SDi. Complete 
the CO sensor testing as follows:

   Spray a UL approved CO agent into the top of the detector near the CO 

sensor opening for at least 1 second. CO sensor opening is indicated by 
a triangle on the sensor cover. (See Figure 3.) Use the applicator straw 
included with the CO agent to more efficiently direct the CO into the detec-
tion cell during testing. 

   The detector will go into alarm if gas entry is successful. It may take up 

to 1 minute for the device to alarm. Once the detector is in alarm allow 
5 minutes for the CO to clear and exit the detector.

  

I56-6638-000 

 

 1/15/2021

Содержание FIK-PC351

Страница 1: ...iance with the control panel system installation manual For local audible indication of a fire and or carbon monoxide alarm it is recommended to install the multi criteria photoelec tric and carbon monoxide CO sensor into a B200S series sounder base If a local audible device is not used care should be taken to develop a proper response plan The installation must meet the requirements of the Author...

Страница 2: ...t The magnet test initiates an approximately 10 minute period when the detec tor s signal processing software routines are not active Once in test mode test the smoke detector using one of the tested and ap proved aerosol smoke products Refer to the manufacturer s published instruc tions for proper use of the canned smoke agent When used properly the canned smoke agent will cause the smoke detecto...

Страница 3: ...s Carbon monoxide gas is a highly poisonous gas which is released when fuels are burnt It is invisible has no smell and is therefore impossible to detect with the human senses Under normal conditions in a room where fuel burn ing appliances are well maintained and correctly ventilated the amount of carbon monoxide released into the room by appliances should not be danger ous SYMPTOMS OF CARBON MON...

Страница 4: ...e and 2 this device must accept any interference received including interference that may cause undesired operation NOTE This equipment has been tested and found to comply with the limits for a Class B digital device pursuant to Part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates use...

Отзывы: