background image

 TWINFLEX

®

pro Control Panel User Guide 

 

 

 

14

 

 

 
 
 
 

FIRE OUTPUT 

Yellow 

Flashing 
 
 
Continuous 

A  fault  condition  is  present  on  a  monitored  Relay 
circuit. 
 
A device or an action associated with the monitored 
relay circuit has been disabled.  
 

DAY 

Yellow 

Continuous 
 

The  system  has  gone  into  the  less  sensitive  day 
mode as programmed. 
 

ROUTINE SERVICE 

Yellow 

Continuous 

The  pre  programmed  service  interval  has  expired 
and  a  weekly  test  or  routine  maintenance  check  is 
due. 
 

DELAY 

Yellow 

Continuous 

An  action  has  been  started  which  utilises  a 
programmed delay. 
 

ALARMS 

Yellow 

Flashing 
 
Continuous 

The alarm sounders have been activated 
 
The  alarm  sounders  have  been  silenced  whilst 
operating, and the system is awaiting a reset. 
 

BUZZER SILENCED 

Yellow 

Continuous 
 
 

The  control  panel  buzzer  has  been  silenced  whilst 
operating and will stay silenced until another fault or 
relevant action occurs. 
 

 
 
 
During a system fault, dependent upon what caused the fault, all relays will be off, all zones will be powered down, the 
zone, power fault and disabled LEDs will be on continuously. If any output is set to sounder then the Sounder LED will 
also be on continuously. 
 
To recover from this the panel should be powered down for approximately 2 minutes and then re-powered. This should 
be done by a competent person and entered in the log at the end of this manual. If the panel appears to be operational, 
then a reset will clear the fault and should be entered into the log at the end of this manual. 
 
The only exception to this is the write enable switch. In access levels 1 and 2, if the switch is on, a system fault will be 
indicated on the LEDs and display, the fault relay will be off but it has no effect on the operation of the panel and serves 
as a reminder to the Engineer to switch off write enable before leaving the panel. 
 
If the display is blank and no LEDs are showing, then either the unit is not powered or the mains has failed and the 
batteries are lower than 21V. To recover from the low battery shut-off, down power completely and check the batteries 
are no lower than 21V and then power up the system. 
 
If  the  batteries  are  lower  than  21V,  then  they  should  be  replaced  or  monitored  during  initial  charging  to  ensure  they 
recharge correctly. This could take several hours. 
 
If the batteries are below 18V they should be replaced as they will have lost much of their capacity and are unlikely to 
recover. This could leave the system with no power under mains fail conditions. 
 

 

SOUNDER  

Yellow 

Flashing 
 
 
Continuous 

A  fault  condition  is  present  on  a  monitored  sounder 
circuit. 
 
A device or an action associated with the monitored 
sounder circuits has been disabled.  
 

PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor

Содержание EP0856828

Страница 1: ...n Alarm System Control Panel Suitable for TWINFLEX pro control panels from V1 00 Control Panel User Guide TO BE RETAINED BY THE USER PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor ...

Страница 2: ...arried out by competent persons Fike cannot guarantee the operation of any equipment unless all documented instructions are complied with without variation E OE TWINFLEX Mulitpoint Fike and Fike Corporation are registered trademarks of Fike Corporation and its subsidiaries All other trademarks trade names or company names referenced herein are the property of their respective owners Fike equipment...

Страница 3: ... Fire Alarm 11 On Hearing the Alarm 11 Accessing the Controls 11 Silencing the Alarms 12 Resetting the System 12 Sounding the Alarms 12 Silencing the Buzzer 12 Exiting Access Level 2A User or Access Level 2B Supervisor 12 LED Indication 13 Troubleshooting 15 Advanced Operation 16 Access Level 1 Normal 16 Access Level 2A User 17 Access Level 2B Supervisor 19 Log Book 24 Fire Alarm System Notice 30 ...

Страница 4: ...on and any other staff who may be required to operate the system in an emergency should read and understand the basic operating instructions before an emergency situation occurs Definitions Responsible person The person having control of the premises whether as an occupier or otherwise or any person delegated by the person having control of the premises to be responsible for the fire alarm system ...

Страница 5: ...alarm The panel also monitors each zone for detector head removal device fault End of line fault and open or short circuit fault The TWINFLEX pro control panel also provides two monitored outputs that may be configured as conventional sounder circuits or conventional 24V monitored relay circuits A volt free common fire relay and a volt free common fault relay are also provided There are also two m...

Страница 6: ...es 2 x 12V 3 3Ah batteries to provide up to a maximum of 72 hour standby times depending on total panel loading Unlike most conventional fire alarm systems which require separate pairs of cables for detector zones and sounder circuits the TWINFLEX pro system requires one 2 core screened cable for each zone to accommodate both detection devices and sounders Furthermore sounders are incorporated wit...

Страница 7: ... parts of the system are disabled Daily Check that the panel indicates normal operation and that any fault is recorded Also check that the recorded faults have been dealt with Weekly At least one detector or call point should be operated to test the ability of the control equipment to receive a signal and sound the alarm In practice it is far easier for the user to activate a manual call point rat...

Страница 8: ...ing the following Always make a note of all illuminated indicators and messages displayed at the control panel Try and identify the activated device ie Do not reset the system until the area of the incident has been inspected Record any other incidents occurring at the same time which could affect the system eg power supply failure building works etc The service organisation will be more likely to...

Страница 9: ... Enabled LED is switched off see Fire Alarm Controls Control Panel Front Note 4 Zone 8 Zone Panel version shown General Indication LEDs Control Panel Information Window Zonal Indication LEDs Fire Alarm Controls Controls enabled keyswitch System Indication LEDs System Controls PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor ...

Страница 10: ...tem automatically prompting you with the relevant options for your Access Level and system status The menus may be navigated in one of two ways as required 1 Use the UP DOWN keys to move the highlighted selection and press ENTER to select the chosen one 2 Enter the desired option number and press ENTER to select it Press the ESC key to exit to the previous menu fire alarm controls turn key to enab...

Страница 11: ...the user A valid access level code must be entered in order to access any of the menus Fire Alarm When the panel enters the fire state the alarms will sound the fire LEDs will illuminate the buzzer will pulse quickly and the display will show the location and type of alarm On Hearing the Alarm The responsible person should have already prepared written procedures for the action to be taken in the ...

Страница 12: ...immediately Sounding the Alarms To sound the alarms at any time after they have been silenced proceed as follows 1 Enable the controls and then press SOUND ALARMS The alarm sounders will activate The buzzer will also switch on Silencing the Buzzer To silence the buzzer press the SILENCE BUZZER button at access level two as above 1 Enable the controls and then press SILENCE BUZZER The fault buzzer ...

Страница 13: ...Continuous A Manual Call Point in the zone indicated is in the alarm state and sending an alarm signal to the panel A Detector in the zone indicated is in the alarm state and sending an alarm signal to the panel SYSTEM FAULT Yellow Continuous Flashing The system Fault LED indicates the presence of a processor or a checksum error Power the system down to clear reprogram all settings and test the sy...

Страница 14: ...tent person and entered in the log at the end of this manual If the panel appears to be operational then a reset will clear the fault and should be entered into the log at the end of this manual The only exception to this is the write enable switch In access levels 1 and 2 if the switch is on a system fault will be indicated on the LEDs and display the fault relay will be off but it has no effect ...

Страница 15: ... operation Alarm condition still present Remove cause of alarm eg reset call point element with key Buzzer sounding FAULT LED lit Fault or abnormal condition Note all illuminated LEDs and displayed messages Call engineer Buzzer sounding POWER FAULT LED flashing Mains supply failed displayed Mains supply failure Wait until mains supply is restored if panel does not revert to normal operation call e...

Страница 16: ...to exit the menu The Active Log will display any current faults These are displayed in text format and may be scrolled through by pressing the UP and DOWN keys Press the ESC key to exit the menu The Active Log will display any current disables These are displayed in text format and may be scrolled through by pressing the UP and DOWN keys Press the ESC key to exit the menu NORMAL 1 View Events 1 Cu...

Страница 17: ...d through by pressing the UP and DOWN keys Press the ESC key to exit the menu The Active Log will display any current disables These are displayed in text format and may be scrolled through by pressing the UP and DOWN keys Press the ESC key to exit the menu USER 8737 1 View Current Events 1 Current Fires 2 Current Faults 3 Current Disables 4 Current Warnings 1 Test Cntrls Disp 2 Test Modes 1 Test ...

Страница 18: ...r operation The test light will illuminate while this action is taken The Test keyboard function enables the user to select each button to ensure the correct function is shown on the screen Press the ESC key TWICE to exit the menu 1 View Current Events 4 Current Warnings 2 Test Modes 1 Test Cntrls Disp 1 Test LCD display 2 Test Modes 1 Test Cntrls Disp 2 Test LEDs 2 Test Modes 1 Test Cntrls Disp 3...

Страница 19: ...ending on actual set up SUPR 7877 1 View Current Events 1 Current Fires 2 Current Faults 3 Enable Disable 1 Remote Fires 2 All Sounders 3 Delays 4 Zone 5 Network Comms 4 Set Time and Date 5 View Logs 1 All Event Logs 2 Fire Logs 3 Fault Logs 4 Panel Event Logs 3 Current Disables 4 Current Warnings 1 Test Cntrls Disp 2 Test Zone 2 Test Modes 1 Test LCD Display 2 Test LEDS 3 Test Buzzer 4 Test Keybo...

Страница 20: ...sing the UP and DOWN keys Press the ESC key to exit the menu The Test Display function causes LCD screen to blacken and the test LED to illuminate The Test LEDs function causes the panel LEDs to toggle on off to test for correct operation when this option is active the test light will be illuminated 1 View Current Events 1 Current Fires 1 View Current Events 2 Current Faults 1 View Current Events ...

Страница 21: ... one or more detection zones to operate in a one man walk test mode with local sound On triggering a device the device LED operates the sounder within that device operates and the event is recorded into the event log as a test activation but the control panel does not show an alarm After approximately 5 seconds the system will reset the device and another may be tested The control panel event log ...

Страница 22: ...vent will be recorded to log This function allows the delays to be temporarily turned off i e set to 0 time delay This function allows the disablement or enablement of a detection zone Thus all the input devices Manual Call Points detectors and inputs within that detection zone will be disabled The control panel will indicate that disablements are present a disablement event will be recorded to lo...

Страница 23: ...may be scrolled through by pressing the UP and DOWN keys Press the ESC key to exit the menu The Fault Log will display a log of any fault conditions received by the panel These are displayed in text format and may be scrolled through by pressing the UP and DOWN keys Press the ESC key to exit the menu The Panel Event Log will display a log of events generated from the panel These are displayed in t...

Страница 24: ...uide 24 LOG BOOK Record all fire and fault events whether or not an engineer was called Event Log Time Zone Device Event Action Initials PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor ...

Страница 25: ...TWINFLEX pro Control Panel User Guide 25 Time Zone Device Event Action Initials PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor ...

Страница 26: ...TWINFLEX pro Control Panel User Guide 26 Time Zone Device Event Action Initials PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor ...

Страница 27: ...TWINFLEX pro Control Panel User Guide 27 Time Zone Device Event Action Initials PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor ...

Страница 28: ...TWINFLEX pro Control Panel User Guide 28 Time Zone Device Event Action Initials PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor ...

Страница 29: ...TWINFLEX pro Control Panel User Guide 29 Time Zone Device Event Action Initials PDF compression OCR web optimization using a watermarked evaluation copy of CVISION PDFCompressor ...

Страница 30: ...To silence the alarm sounders press SILENCE ALARMS Following a Fire Alarm Operation The red FIRE LEDs will illuminate the fire alarms and the internal buzzer will operate as programmed Take appropriate action as defined by the emergency plan for the premises To silence the alarm press SILENCE ALARMS then establish the cause of the alarm and enter the details in the log book Reset any Manual Call P...

Страница 31: ...nly is sounding then check your own area for the cause of the alarm If this proves to be a false alarm due to dust cooking fumes steam cigarette smoke etc then clear the smoke steam from the area in order to allow the system to reset itself after a few minutes If this happens then no further action is required If the sounders in the communal areas are also sounding then follow the buildings fire r...

Страница 32: ...quipment Control Panel TWINFLEX pro V Serial No No of Zones used Mains Supply Zone 1 Zone 2 Zone 3 Zone 4 Zone 5 Zone 6 Zone 7 Zone 8 Total No of Devices No of Detectors No of Call Points No of Sounders No of I O Interfaces Access Level 2A User code Default USER Access Level 2B Supervisor code Default SUPR Test Certificate number In an emergency call Normal Hours Out of Hours PDF compression OCR w...

Отзывы: