TWINFLEX
®
pro Control Panel User Guide
22
The System Test function allows the entire system to operate in a simple one-
man walk test mode. On triggering a device the device LED operates and the
event is recorded into the event log, all the assigned sounders operate for 10
seconds and the control panel indicates an alarm. After approximately 10
second the system will reset the device, and another may be tested. The
control panel event log will indicate that a test mode has been selected.
Please note, with the system test mode, only the sounders assigned to
operate from that device will sound, and any delays will still be present. i.e., if
a delay of 2 minutes is present, the system will have been reset before the
sounders activate.
N.B. To put ALL zones into test enter 00 for the zone number.
This function allows the global disablement or enablement of all fire outputs
on the panel. The control panel will indicate that disablements are present and
a disablement event will be recorded to log.
This function allows the global disablement or enablement of all the sounders
on the system. The control panel will indicate that disablements are present
and a disablement event will be recorded to log.
This function allows the delays to be temporarily turned off (i.e. set to 0 time
delay).
This function allows the disablement or enablement of a detection-zone. Thus,
all the input devices (Manual Call Points, detectors and inputs) within that
detection-zone will be disabled. The control panel will indicate that
disablements are present, a disablement event will be recorded to log, the
device LED will still operate when activated and an event will be recorded to
log, but no programmed actions will occur. The sounder within the device will
still operate if triggered from elsewhere on the system.
2. Test Modes
2. Test Zone
3. System Test
3. Enable/ Disable
1. Remote Fires
3. Enable/ Disable
2. All Sounders
3. Enable/ Disable
3. Delays
3. Enable/ Disable
4. Zone
01/09/09 22:26 SUPR
SYSTEM TEST (ZONES)
ENTER ZONE:00
Press Enter Key
01/09/09 22:26 SUPR
TEST ALL ZONES
1.START 2.END
Press <> OR Esc Key
01/09/09 22:26 SUPR
REMOTE FIRE:DISABLED
1.DISABLE 2.ENABLE
Press <> OR Esc Key
01/09/09 22:26 SUPR
SOUNDERS:DISABLED
1.DISABLE 2.ENABLE
Press <> OR Esc Key
01/09/09 22:26 SUPR
DELAYS: ENABLED
1.DISABLE 2.ENABLE
Press <> or Esc Key
01/09/09 22:26 SUPR
ZONE(ENABLE/DISABLE)
ENTER ZONE:00
Press Enter Key
01/09/09 22:26 SUPR
ZONE: ENABLED
1.DISABLE 2.ENABLE
Press <> OR Esc Key