ECS Series Manual —  

P/N LS10262-001FK-E:A  3/3/2021

55

Installing the FIK-DUAL50W

Device Installation

4.7.8  Setting the FIK-DUAL50W Mode

Figure 4.52  DIP Switch Modes

When the FIK-DUAL50W is connected to an FCP-300ECS or FCP-2100ECS, the mode is set using the HFSS Programming Tool and the 
DIP switch mode selector is ignored. 

The amplifier modes are as follows:

50 Watt with Backup - Amp A powers Audio Circuits 1 - 8. Amp A is backed up by on-board Amp B. (Default, DIP setting at 2).

100 Watt with no Backup - Amp A powers Audio Circuits 1 - 4. Amp B powers Audio Circuits 5 - 8. There is no backup. (DIP setting 
at 1).

100 Watt with Backup (requires FIK-50WBU) - Amp A powers Audio Circuits 1 - 4. Amp B powers Audio Circuits 5 - 8. The FIK-
50WBU will backup Amp A or Amp B but never both. (DIP setting at 3).

If the FIK-DUAL50W is connected to an FCP-2100ECS system and configured to operate in a dual channel setup, Amp A and/or Amp B is 
not restricted to which audio circuits it can power. However, both can never power the same audio circuit.

4.7.9  Test Switch use

SW1 - AMP A

Switch should be moved to the “ON” position for normal operation. Move this switch to the “Test” position to test backup amplifier.

SW2 - AMP B

Switch should be moved to the “ON” position for normal operation. Move this switch to the “Test” position to test backup amplifier.

NOTE:

Please allow up to 3 minutes for backup amplifier to engage.

4.7.10  Connecting AC Power

At installation, connect the AC terminals to the power source as shown in Figure 4.53. It may be necessary for a professional electrician to 
make this connection.

The AC terminals are rated as 120VAC, 60 Hz or 240VAC, 50/60 Hz.

Figure 4.53  AC Connection

Содержание ECS Series

Страница 1: ...A P N LS10262 001FK E A ECN 151526 Document LS10262 001FK E 3 3 2021 Rev Emergency Communication System ECS Series Installation Operation Manual ...

Страница 2: ...ches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least once per year by a qualified fire protection specialist Heat detectors are designed to protect property not life IMPORTANT Smoke detectors must be installed in the same room as the control panel and in rooms used ...

Страница 3: ...ior to any drilling filing ream ing or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifications verify that they will not interfere with battery transformer or printed circuit board location Do not tighten screw terminals more than 9 in lbs Over tightening may damage threads resulting in reduced terminal contact pressure and difficulty with ...

Страница 4: ...ail us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for printed manual Brief description of content you think should be improved or corrected Your suggestion for how to correct improve documentation Send email messages to FikeElectSupport fike com or call 800 979 3453 x21 in US or 816 22...

Страница 5: ... or FIK LOC2100 Cabinet 17 3 4 6 Surface Mounting Instructions 18 Section 4 Device Installation 20 4 1 Connecting AC Power and Batteries 20 4 2 Installing the FIK NVCM 20 4 2 1 FIK NVCM Board Layout 20 4 2 2 Installing and Connecting the FIK EMG to the FIK SW24 21 4 2 3 FIK NVCM Fiber Modules 24 4 2 4 Installing the Microphone 24 4 3 Installing the FIK 50W 25 4 3 1 FIK 50W Board Layout 26 4 3 2 Mo...

Страница 6: ... the FIK DUAL50W Mode 55 4 7 9 Test Switch use 55 4 7 10 Connecting AC Power 55 4 7 11 Backup Battery for FIK DUAL50W 56 4 7 12 Calculating Current Draw and Standby Battery 56 4 8 Installing the FIK 50WBU 56 4 8 1 FIK DUAL50W Board Layout 57 4 8 2 Installing the FIK 50WBU 57 4 9 Installing the FIK CE4 58 4 10 Installing the FIK RVM 59 4 10 1 FIK RVM Board Layout 59 4 10 2 Wiring the FIK RVM 60 4 1...

Страница 7: ...K LOCs FCP 2100ECS Systems can support up to 15 FIK 2100LOCs Mappable Speaker Circuits FCP 300ECS systems can support up to 64 mappable speaker circuits using a combination of FIK 50Ws FIK 125Ws FIK DUAL50Ws and FIK CE4s FCP 2100ECS systems can support up to 128 mappable speaker circuits using a combination of the FIK 50W FIK 125W FIK DUAL50W FIK INT50W and FIK CE4 Backup Amplifier FIK DUAL50Ws ar...

Страница 8: ...r an ECS event on the FCP 2100ECS ECS LOC Priority The priority level which is programmed for every ECS LOC In order from lowest to highest Low Normal High ECS Super User A user profile provided option that allows the user to override all ECS Control rules and gain ECS Control VBUS The VBUS is an analog voice bus that carries the recorded voice messages from the FIK NVCM to the FIK 50W FIK 125Ws o...

Страница 9: ...ECS Series Manual P N LS10262 001FK E A 3 3 2021 9 Notes ...

Страница 10: ...hose specified in the FACP manual 4 A full system checkout must be performed any time the panel is programmed Restricted Options The loss of AC signal is defaulted to 3 hours however the system allows settings from 0 3 hours For UL certified installations this number must be set from 1 to 3 hours The system allows the use of non latching spot type smoke detectors This feature may not be used in co...

Страница 11: ...stems Minimum system requirements are one Honeywell Silent Knight addressable initiating device and either a 5220 Keltron 3158 or the built in Digital Alarm Communicator Transmitter DACT 1 Do not exceed the current load restrictions shown in Section 3 of FACP manual 2 The AC Loss Hours option must be set from 1 3 hours 2 2 5 Requirements for the Installation of Carbon Monoxide CO Detection and War...

Страница 12: ...ith telephone communication or cause false alarms To avoid induced noise follow these guidelines Isolate input wiring from high current output and power wiring Do not pull one multi conductor cable for the entire panel Instead separate the wiring as follows Do not pull wires from different groups through the same conduit If you must run them together do so for as short a distance as possible or us...

Страница 13: ...ECS Series Manual P N LS10262 001FK E A 3 3 2021 13 Wiring Specifications Installation Figure 3 1 Wire Routing FCP 300ECS SLC devices Phone Lines AC Power Input SBUS devices ...

Страница 14: ...0 60 Hz 200 mA 600 mA FIK 50W 70V 120V 60 Hz 350 mA 1200 mA FIK 50W 70V 240V 50 60 Hz 200 mA 600 mA Table 3 1 FIK 50W AC Current Draw Module Voltage Standby Current Alarm Current FIK 125W 25V 120V 60 Hz 300 mA 2200 mA FIK 125W 25V 240V 50 Hz 250 mA 1250 mA Table 3 2 FIK 125W AC Current Draw Module Voltage Standby Current Alarm Current FIK DUAL50W 25V 120V 60 Hz 210 mA 2510 mA FIK DUAL50W 25V 240V ...

Страница 15: ...ions to prevent water from entering the cabinet Water damage is not covered under warranty 3 4 2 Surface Mounting the FCP 300ECS FCP 2100ECS or FIK LOC Cabinet The cabinets can be mounted on the wall surface by using the mounting holes in the back of the cabinet see Figure 3 3 The FIK LOC Local Operating Console is a combination FIK RVM Remote Voice Module and its associated annunciator The FIK LO...

Страница 16: ...mounting holes in the back of the cabinet see Figure 3 4 The FIK LOC is a combination FIK RVM Remote Voice Module and its associated FIK RA2000 annunciator The FIK LOC is compatible with the FCP 300 For more information refer to Installation manuals for the FACP Cabinet dimensions are 20 362 W x 27 H x 5 054 D Figure 3 4 FIK LOC Cabinet Mounting Holes 27 20 362 Bottom Mounting Holes Key Shaped Hol...

Страница 17: ...re 3 5 For more informa tion refer to Installation manual for FCP 300ECS P N LS10145 002FK E Cabinet backbox dimensions are 26 5 H x 20 W x 4 1 D Figure 3 5 FCP 300ECS Cabinet Mounting Holes 3 4 5 Surface Mounting the FCP 2100ECS or FIK LOC2100 Cabinet The FIK LOC2100 is a combination FIK RVM Remote Voice Module and its associated FIK RA2000 annunciator The FIK LOC2100 is compatible with the FCP 2...

Страница 18: ... Surface Mounting Instructions The ECS Series cabinets can be mounted on the wall surface by using the mounting holes in the back of the cabinet see Figure 3 7 1 Insert two screws level with each other 16 apart for the top cabinet key shaped holes See Figure 3 7 2 Hang the cabinet onto the two screws Tighten the screws down 3 Insert two screws into the two bottom mounting holes and tighten them sn...

Страница 19: ...dead front panel for the FCP 300ECS or the FCP 2100ECS 1 Disconnect the connection between the FIK NVCM and the FIK EMG keypad 2 Disconnect VBUS wiring from FIK NVCM 3 Slide the door or dead front over two pins in the hinge bracket of the base The outer hinge pins are for the door the inner hinge pins are for the dead front See Figure 3 11 Figure 3 7 Cabinet Door and Dead Front Panel Removal To re...

Страница 20: ... Module The FIK NVCM is compatible with the FCP 2100ECS and FCP 300ECS FACPs For more information on how to install or remove the FIK NVCM Network Voice Control Module see installation sheet PN LS10169 002FK E 4 2 1 FIK NVCM Board Layout Figure 4 1 Front View of FIK NVCM ECS Series Model Number FACP Installation Manual FCP 300ECS LS10145 002FK E FCP 2100ECS LS10143 002FK E Network Connector P4 Key...

Страница 21: ...cting the FIK EMG to the FIK SW24 The FIK SW24 adds 24 switches to the FCP 300ECS and FCP 2100ECS controls for a total of 40 with the 16 Non ECS switches on the FIK EMG Follow these steps to install and connect the FIK SW24 1 Open Cabinet door and dead front panel 2 Remove AC power from the main control panel 3 Disconnect the backup batteries Microphone Connection FIK SW24 Connector FIK NVCM Conne...

Страница 22: ...FIK SW24 as shown in Figure 4 5 6 For the FCP 2100ECS connect one end of the wiring harness PN 130398 supplied to the FIK EMG and the other end to the P4 connector on the FIK NVCM as shown in Figure 4 6 If two FIK SW24 s are used connect one FIK SW24 to the other FIK SW24 as shown in Figure 4 7 7 Secure the switch expander s to the dead front panel using the supplied six Hex nuts 8 Restore AC powe...

Страница 23: ...s Manual P N LS10262 001FK E A 3 3 2021 23 Installing the FIK NVCM Device Installation Figure 4 6 Wiring Harness Connection for the FIK NVCM to FCP 2100ECS Figure 4 7 Connection between FIK EMG and Two FIK SW24s ...

Страница 24: ...on modules to convert wire to fiber For more information see Installation sheet PN LS10178 002FK E FIK FML Fiber Optic Multi Mode Receiver FIK FSL Fiber Optic Single Mode Transmitter 4 2 4 Installing the Microphone To install the microphone follow these steps 1 Clip the microphone into the micro phone clip See Figure 4 8 Figure 4 8 Hang Microphone on to Microphone Clip ...

Страница 25: ...t Panel Hole 3 Attach strain relief clip to microphone cord The strain relief clip should have about 2 of micro phone cord through it See Figure 4 10 4 Push the strain relief into the hole in the dead front panel 5 Connect microphone to appropriate connector on FIK EMG Figure 4 10 Installing Strain Relief Clip 4 3 Installing the FIK 50W This section provides information on how to install the FIK 5...

Страница 26: ...in a secured area but should be accessible for testing and service Mount the control panel cabinet so it is firmly secured to the wall surface When mounting on concrete especially when moisture is expected attach a piece of plywood to the concrete surface and then attach the cabinet to the plywood Also mount any other modules to the plywood The cabinet can be surface or flush mounted If you will b...

Страница 27: ...ut and power wiring Avoid pulling one multi conductor cable for the entire panel Instead separate the wiring as follows DO NOT pull wires from different groups through the same conduit Twisted shielded wire is recommended for all audio circuits to provide the maximum protection against EMI and AFI emission and suscep tibility If using shielded cable attach the shield to earth ground on the control...

Страница 28: ...r circuit is capable of 50 watts of power at 25 Vrms or 70 7 Vrms Wiring Lengths Number Of Speakers Total Load Wire Distance in Feet 1 2 W 1 W Vrms Watts 18 AWG 16 AWG 14 AWG 12 AWG 10 5 25Vrms 5W 3900 6200 9860 15680 70Vrms 25000 39700 63200 100520 20 10 25Vrms 10W 2125 3380 5375 8540 70Vrms 15200 24150 38400 61100 30 15 25Vrms 15W 1460 2320 3690 5870 70Vrms 11000 17500 27800 44200 40 20 25Vrms 2...

Страница 29: ...gure 4 15 illustrates how to wire speakers to the control panel using Class A wiring Figure 4 15 Class A Speaker Configuration 4 3 5 VBUS Wiring The VBUS is an analog voice bus that carries the recorded voice messages from the FIK NVCM to the FIK 50W or the voice messages gen erated from a system microphone to the FIK 50W The maximum resistance on the VBUS is 20Ω Connect the VBUS from the FIK NVCM...

Страница 30: ...ation on how to connect FIK 50Ws up to 8 for FCP 300ECS or up to 16 for FCP 2100ECS onto the main con trol SBUS Refer to Section 4 1 for SBUS specifications Wire the SBUS as shown in Figure 4 17 or Figure 4 18 Figure 4 17 SBUS Connections of the FIK 50W 15kΩ EOL at last panel on the VBUS Supervised power limited VBUS Connections 3 Vrms 5mA max FIK NVCM FIK 50W FIK 50W Control Panel ...

Страница 31: ...ormer P N 115061 To install the AC transformer into the FIK 50W cabinet follow these steps 1 Open the cabinet door 2 To access cabinet interior open dead front panel by removing the upper screw and the mid door retaining screw 3 Mount the transformer onto the threaded cabinet transformer mounting studs using the supplied locking hex nuts as shown in Figure 4 19 Figure 4 19 Transformer Mounting Sup...

Страница 32: ... Plug the transformer output to the AC connector on the control panel as shown in Figure 4 20 4 3 8 Backup Battery for FIK 50W The following steps explain how to connect the batteries refer to Figure 4 21 1 Connect the black wire of the battery harness to the side of the battery 2 2 Connect the jumper wire provided form the positive side of battery 2 to the negative side of battery 1 ...

Страница 33: ... Hours per system Device No of Devices Current Per Device Standby Current Alarm Current FIK 50W 25V 1 Standby 85 mA 85 mA Alarm 525 mA 525 mA FIK 50W 70 7V 1 Standby 100 mA 100 mA Alarm 580 mA 580 mA FIK CE4 0 or 1 Standby 20 mA 20mA Alarm All Channels 180 mA 180 mA A Current Subtotals mA mA Notification Devices Refer to device manual for number of devices and current ratings B Current Subtotals m...

Страница 34: ...or the Emergency Communication System 4 4 1 Board Layout Mounting Figure 4 22 Front View of FIK INT50W Mounting the FIK INT50W 1 Remove AC power and disconnect the backup batteries from the main control panel 2 To mount the FIK INT50W inside the FACP cabinet under the main board align the board with the mounting holes Secure the board to the enclosure with the supplied screws See Figure 4 23 Figur...

Страница 35: ...pplied screws Orientate with Top side up see Figure 4 24 Secure the FIK INT50W onto the six standoffs making sure the two coil parts are at the top and on the right side of the FIK AMPMT See Figure 4 25 and Figure 4 25 for coil position Figure 4 24 FIK AMPMT installed in Cabinet Figure 4 25 FIK INT50W Installed using the FIK AMPMT Top Mounting Holes FIK AMPMT ...

Страница 36: ...d in FCP 2100ECS Cabinet 4 4 2 Wiring to a FACP See Figure 4 27 to properly wire the FIK INT50W to the FACP The Internal Amplifier must be powered by a NAC programmed as Constant Auxiliary Power Refer to the FACP installation manual Figure 4 27 Wiring the FIK INT50W to the FACP Install with coils to the top right FACP FIK INT50W ...

Страница 37: ...50W supplies one circuit for speaker connection The speaker circuit can be supervised and wired Class B or Class A The speaker circuit is capable of 50 watts of power at 25 Vrms or 70 7 Vrms See Section for wire lengths 4 5 1 Calculating Current Draw and Standby Battery This section helps you determine the current draw and standby battery needs for your installation Complete the remaining instruct...

Страница 38: ...Devices Refer to device manual for number of devices and current ratings B Current Subtotals mA mA C Total current rating of all devices in system Line B X 0 001 A A D Number of standby hours 24 or 60 for NFPA 72 H E Multiply line C standby current and D Total standby AH AH F Alarm sounding period in hours For example 5 minutes 0 0833 hours H G Multiply line C alarm current and F Total alarm AH AH...

Страница 39: ...ill be flush mounting the cabinet the hole for the enclosure should be 14 5 W x 24 75 H x 3 7 16 D 36 8cm W x 62 9cm H x 8 73cm D Do not flush mount in a wall designated as a fire break The Outside dimensions of the cabinet are 16 W x 26 1 4 H x 4 1 8 D 40 64cm W x 66 68cm H x 10 48cm D Follow these steps to properly mount the cabinet 1 On the mounting surface install two screws level with each ot...

Страница 40: ...e board to the enclosure 6 Restore AC power and reconnect the backup batteries Figure 4 32 FIK 125WBD In Enclosure 4 6 4 Wiring Specifications All wiring and devices installed in the system must meet the standards described in National Electrical Code NFPA 70 NFPA Standard 72 and Life Safety Code NFPA 101 To avoid induced noise transfer of electrical energy from one wire to another keep input wiri...

Страница 41: ...ncy noise such as that produced by the inductive reactance of a speaker or bell can also be reduced by running the wire through ferrite beads or by wrapping it around a ferrite toroid core Figure 4 33 provides an example Figure 4 33 Wire Routing Example for the FIK 125W 4 6 5 Speaker Wiring Each FIK 125W supplies four NACs Notification Appliance Circuits for speaker connection The speaker circuit ...

Страница 42: ...e in Feet 1 2 W 1 W Vrms Watts 18 AWG 16 AWG 14 AWG 12 AWG 10 5 25Vrms 5W 3900 6200 9860 15680 20 10 25Vrms 10W 2125 3380 5375 8540 30 15 25Vrms 15W 1460 2320 3690 5870 40 20 25Vrms 20W 1100 1750 2780 4420 52 26 25Vrms 26W 760 1200 1920 3050 80 40 25Vrms 40W 550 875 1390 2200 100 50 25Vrms 50W 450 715 1130 1800 150 75 25Vrms 75W 300 476 753 1200 200 100 25Vrms 100W 225 357 565 900 250 125 25Vrms 1...

Страница 43: ...n the VBUS is 20Ω Connect the VBUS from the FIK NVCM to the FIK 125W as shown in Figure 4 36 Figure 4 36 VBUS Wiring for FIK NVCM 4 6 7 SBUS Wiring This section contains information on how to connect FIK 125Ws up to 8 for FCP 300ECS up to 16 for FCP 2100ECS onto the main con trol SBUS Refer to Section 4 of the FACP s Installation manual for SBUS specifications Wire the SBUS as shown in Figure 4 37...

Страница 44: ... 4 38 Connecting Multiple FIK 125Ws to the SBUS using FIK NVCM See Section 4 11 for information on setting SBUS addresses 4 6 8 Connecting AC Power At installation connect the AC terminals to the power source as shown in Figure 4 39 It may be necessary for a professional electrician to make this connection FIK 125W FACP FIK NVCM FIK 125W FACP FIK NVCM FIK 125W ...

Страница 45: ...the battery harness to the side of the battery 2 2 Connect the jumper wire provided form the positive side of battery 2 to the negative side of battery 1 3 Connect the red wire from the battery harness to the positive side of battery 1 Figure 4 40 Battery Connection to FIK 125W 4 6 10 Calculating Current Draw and Standby Battery This section helps you determine the current draw and standby battery...

Страница 46: ...by Current Alarm Current FIK 125W 120V 1 Standby 375 mA 375mA Alarm 700 mA 700mA FIK 125W 240V 1 Standby mA mA Alarm mA mA FIK CE4 0 or 1 Standby 20 mA 20mA Alarm All Channels 180 mA 180mA A Current Subtotals mA mA Notification Devices Refer to device manual for number of devices and current ratings B Current Subtotals mA mA C Total current rating of all devices in system Line B X 0 001 A A D Numb...

Страница 47: ...close to the center of the building as possible and located within a secured area but should be accessible for testing and service Mount the control panel cabinet so it is firmly secured to the wall surface When mounting on concrete especially when moisture is expected attach a piece of plywood to the concrete surface and then attach the cabinet to the plywood Also mount any other modules to the p...

Страница 48: ...e cabinet onto the two mounting screws and tighten the screws 3 Insert two screws into the two bottom mounting holes 4 7 3 Mounting the FIK DUAL50WBD Board Only 1 Make certain that AC and DC power have been removed from the panel 2 If this module is a replacement for an existing FIK DUAL50W remove the screws which secure the board to the enclosure Bottom mounting holes Key Holes Board mounting bra...

Страница 49: ...ications All wiring and devices installed in the system must meet the standards described in National Electrical Code NFPA 70 NFPA Standard 72 and Life Safety Code NFPA 101 To avoid induced noise transfer of electrical energy from one wire to another keep input wiring isolated from high current output and power wiring Avoid pulling one multi conductor cable for the entire panel Instead separate th...

Страница 50: ... printed circuit board where it could induce noise into the sensitive microelectronics or pick up unwanted RF noise from the high speed circuits High frequency noise such as that produced by the inductive reactance of a speaker or bell can also be reduced by running the wire through ferrite beads or by wrapping it around a ferrite toroid core See Figure 4 45 Figure 4 45 Wire Routing Example for FI...

Страница 51: ...0 15680 70Vrms 25000 39700 63200 100520 20 10 25Vrms 10W 2125 3380 5375 8540 70Vrms 15200 24150 38400 61100 30 15 25Vrms 15W 1460 2320 3690 5870 70Vrms 11000 17500 27800 44200 40 20 25Vrms 20W 1100 1750 2780 4420 70Vrms 8500 13510 21500 34175 52 26 25Vrms 26W 760 1200 1920 3050 70Vrms 6100 9700 15400 24520 80 40 25Vrms 40W 550 875 1390 2200 70Vrms 4100 6500 10360 16480 100 50 25Vrms 50W 450 715 11...

Страница 52: ... 7 6 VBUS Wiring The VBUS is an analog voice bus that carries the recorded voice messages from the FIK NVCM to the FIK DUAL50Ws or the voice mes sages generated from a system microphone to the FIK DUAL50Ws The maximum resistance on the VBUS is 20Ω The FIK DUAL50W supports two VBUS channels The wiring method is the same for both channels VBUS1 and VBUS2 should never be wired together Connect the VB...

Страница 53: ... A 3 3 2021 53 Installing the FIK DUAL50W Device Installation Figure 4 48 VBUS Wiring for Single Channel for FIK NVCM Figure 4 49 VBUS2 Wiring for Dual Channel for FIK NVCM FIK DUAL50W FIK DUAL50W FIK NVCM FIK DUAL50W FIK DUAL50W FIK NVCM ...

Страница 54: ...p to 16 for the FCP 2100ECS onto the main control SBUS Refer to Section 4 of the FACPs Installation manual for SBUS specifications Wire the SBUS as shown in Figure 4 50 or Figure 4 51 using the FIK NVCM Figure 4 50 SBUS Connections to the FIK DUAL50W Figure 4 51 SBUS Connections to Multi FIK DUAL50Ws See Section 4 11 for information on setting SBUS addresses FACP FACP FIK DUAL50W To next FIK DUAL5...

Страница 55: ...ackup Amp A or Amp B but never both DIP setting at 3 If the FIK DUAL50W is connected to an FCP 2100ECS system and configured to operate in a dual channel setup Amp A and or Amp B is not restricted to which audio circuits it can power However both can never power the same audio circuit 4 7 9 Test Switch use SW1 AMP A Switch should be moved to the ON position for normal operation Move this switch to...

Страница 56: ...ry Battery Cabinet Maximum of 35 amp hr for the system 4 8 Installing the FIK 50WBU The FIK 50WBU provides backup capability when operating the FIK DUAL50W in the 100 watt with backup mode for both single and dual channel setups The FIK 50WBU mounts above the FIK DUAL50W board on the standoffs provided Device No of Devices Current Per Device Standby Current Alarm Current FIK DUAL50W 25V 1 Standby ...

Страница 57: ... FIK DUAL50W board Figure 4 55 Layout of FIK 50WBU 4 8 2 Installing the FIK 50WBU Follow these steps to install the FIK 50WBU 1 Make sure that all power supplied to the FIK DUAL50W is removed 2 Connect the backup amplifier cable harness P N 50116775 001 from the connector labeled Backup Amplifier on the FIK DUAL50W to the connector on the FIK 50WBU as shown in Figure 4 56 FIK 50WBU ...

Страница 58: ...g the 4 supplied screws mount the FIK 50WBU to the standoff s as shown in Figure 4 56 Figure 4 56 Mounting the FIK 50WBU 4 9 Installing the FIK CE4 The FIK CE4 adds four audio circuits to the FIK 50W and FIK 125W The FIK CE4 mounts inside the FIK 50W or FIK 125W cabinet FIK 50WBU Standoff cable harness ...

Страница 59: ...nector on the FIK CE4 as shown in Figure 4 58 Figure 4 58 Audio Expander Wire Harness Connections 3 Wire audio circuits as shown in Section Speaker Wiring on page 28 4 10 Installing the FIK RVM The FIK RVM Remote Voice Module is contained within the FIK LOC or FIK LOC2100 Local Operator Console It provides a supervised microphone for live communication and an interface for the Emergency Communicat...

Страница 60: ...f FIK RVM 4 10 2 Wiring the FIK RVM 1 Refer to Figure 4 60 to properly connect the FIK RVM to the FACP s SBUS Figure 4 60 SBUS Connections VBUS Microphone connector SBUS Address DIPs AUX Dead front panel SBUS Audio Input AUX Audio Trigger mounting holes Not Used FIK SW24 connector Supervised power limited FIK RVM FACP ...

Страница 61: ...nunciator and FIK RVM See Figure 4 61 Figure 4 61 SBUS wiring for FIK RVM 4 Set the SBUS address on the annunciator and the FIK RVM board See Section 4 11 5 Connect the FIK RVM to the VBUS FIK 125W and FIK NVCM See Figure 4 62 Figure 4 62 VBUS and FIK 125W Wiring for FIK RVM using the FIK NVCM From Previous SBUS Device Annunciator FIK RVM FIK 125W FIK RVM FIK NVCM ...

Страница 62: ...e clip See Figure 4 63 Figure 4 63 Hang Microphone on to Microphone Clip 2 Insert Microphone cord through hole at the bottom of the dead front panel See Figure 4 64 Figure 4 64 Microphone Cord Inserted Through Dead Front Panel Hole 3 Attach strain relief clip to microphone cord The strain relief clip should have about 2 of micro phone cord through it See Figure 4 65 Figure 4 65 Installing Strain R...

Страница 63: ...onnect any devices connected to the VBUS See Figure 4 59 4 Unplug the microphone from the microphone connector See Figure 4 66 Figure 4 66 Back View of FCP 300ECS or FCP 2100ECS Dead Front Panel 5 Remove the six hex nuts that hold the FIK RVM in place 6 Lift the FIK RVM off of the dead front panel 4 11 Addressing SBUS Devices When installing a hardware module such as FIK 6815 FIK 5824 FIK RA1000 F...

Страница 64: ...d their correlation to a numerical ID For example to select ID 2 place DIP switch 2 in the up position Figure 4 67 Possible Module Addresses More information regarding ECS operations Please refer to the ECS section of the FACP s installation manual ECS Series Model Number FACP Installation Manual FCP 300ECS LS10145 002FK E FCP 2100ECS LS10143 002FK E ...

Страница 65: ...ECS Series Manual P N LS10262 001FK E A 3 3 2021 65 ...

Страница 66: ...FIKE CORPORATION 704 SW 10th Street Blue Springs MO 64015 Telephone 1 816 229 3405 www fike com ...

Отзывы: