Duonet Control Panel User Guide
6
User Responsibilities
Introduction
The responsible person is required under BS5839 to undertake certain tasks with respect to the
testing and maintenance of the fire alarm system. The responsible person should also ensure that
written procedures are in place for the actions to be taken by the occupants in a fire condition, and
that staff required to operate the system have received adequate training. In a small building the fire
procedures can be quite simple, but when larger premises are involved the fire procedures can
become more complex and may involve the appointment of fire wardens, reporting procedures,
various assembly points, etc.
The responsible person is also required to liaise with the building maintenance personnel to ensure
that their work does not impair or otherwise affect the operation of the fire alarm system, and to
ensure that a clear space is maintained in the vicinity of detectors, and call points remain unobstructed
and conspicuous.
Routine Testing
The responsible person should also ensure that the following routine testing is carried out. If there is a
link to a remote monitoring centre it will be necessary to advise the centre prior to a test, or use the
control panel facilities to isolate the link. On larger systems it may be necessary to isolate building
services interfaces to avoid disruption to the occupants. In any case the panel should provide audible
and visual indication that parts of the system are disabled.
Daily
Check that the panel indicates normal operation and that any fault is recorded. Also check that the
recorded faults have been dealt with.
Weekly
At least one detector or call point should be operated to test the ability of the control equipment to
receive a signal and sound the alarm.
In practice it is far easier for the user to activate a manual call point, rather than a detector which
requires special equipment. A different device should be tested each time if possible, such that each
zone on the system is tested at least once in a 13 week period.
The results should be recorded in the log book.
Quarterly
‘The responsible person should ensure that every three months the following check is carried out by a
competent person’
In other words the system should be checked by a fire alarm service organisation. This may be the
system installer or an approved maintenance company, and is normally arranged via a maintenance
agreement which specifies the number of visits and the level of service. The agreement should also
cover non-maintenance visits, eg. call outs to attend faults, etc.
The standard specifies a number of maintenance tasks which include a visual inspection of the
installation to ensure that there are no alterations or obstructions which could affect the operation of
the system, and functional checks to confirm the operation of the system.
Содержание DUONET
Страница 22: ...Duonet Control Panel User Guide 22 Time Zone Device Event Action Initials ...
Страница 23: ...Duonet Control Panel User Guide 23 Time Zone Device Event Action Initials ...
Страница 24: ...Duonet Control Panel User Guide 24 Time Zone Device Event Action Initials ...
Страница 25: ...Duonet Control Panel User Guide 25 Time Zone Device Event Action Initials ...
Страница 26: ...Duonet Control Panel User Guide 26 Time Zone Device Event Action Initials ...
Страница 27: ...Duonet Control Panel User Guide 27 Time Zone Device Event Action Initials ...