HIGH LEVEL INTERFACE
18
P/N 06-158
UL S3217
Rev 5, 02/2015
FM 3020297
4.2.6 VESDA RELEASE FEATURES (NOT AVAILABLE IN CYBERCAT)
From the VESDA configuration menu, press F4
V E S D A
Z O N E
N U M :
0 0 1
P R E - D I S C H
T Y P E :
A - A L
P R E - D I S C H
L E V : F I R E
2
C O U N T D O W N :
A U T O M A T I C
Exhibit 18: VESDA Release Menu
Line 1
VESDA Detector Zone number. Arrow under the field, and use the +/- button to change the
VESDA detector zone number.
Line 2
There are six (6) different Pre-Discharge types available for each addressable input device. This
selection will tell the panel how this VESDA should participate with the Suppression zone.
(See Cheetah Xi Product Manual, Appendix 4, for definition of each of these Pre-Discharge
types, A-F).
Line 3
Select the VESDA Fire level to participate in Pre-Discharge events, Fire 1 or Fire 2.
(Only if Pre-Discharge type selected on Line 2 is not ‘A’ for an Alarm Only
Line 4
Countdown time for the system to operate when this device is activated, automatic or manual.
These countdown times are set up in the zone configuration.
L
Note:
The VESDA Compact detector can participate in pre-discharge on the Cheetah Xi panel, since Fire
1 level may be selected to participate in pre-discharge operation.