5.2
Client Side Node Parameters
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up
to
32
alphanumeric
characters
Node_ID
The eLumen processor address. Only decimal values are
allowed: e.g. 11 hex must be entered as 17.
0-255
Protocol
Specify protocol used
eLumen
Connection
Specify which port the device is connected to the
FieldServer
P1-P8, R1-R2
Node_Type
Specifies the eLumen command and data format
Hex, Decimal
Example
// Client Side Nodes
Nodes
Node_Name , Node_ID , Protocol , Port , Node_Type
LUT_GRF6_0 , 17
, eLumen
, P1 , Hex
5.3
Client Side Map Descriptors
5.3.1
FieldServer Related Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up to 32 alphanumeric characters
Data_Array_Name
Name of Data Array where data is
to be stored in the FieldServer
One of the Data Array names specified in Section
4.
Data_Array_Offset
Starting location in Data Array
0 to (Data_Array_Lenght -1) as defined in
Section 4.
Function
Function of Client Map Descriptor
Arco, Awt, Rdbc, Passive_Client, Arcs. Refer to