![FieldServer Lutron Machine FS-8700-97 Скачать руководство пользователя страница 11](http://html.mh-extra.com/html/fieldserver/lutron-machine-fs-8700-97/lutron-machine-fs-8700-97_driver-manual_2287902011.webp)
FS-8700-97 Lutron Machine Manual
Page 11 of 24
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
Preloads
Data_Array_Name , Preload_Data_Format , Preload_Data_Value , Location
// Binary Output Object ID 1
Script_list_BO
, Uint16
, 1
, 0
Script_list_BO
, Uint16
, 2
, 1
// Binary Output Object ID 2
Script_list_BO
, Uint16
, 3
, 2
Script_list_BO
, Uint16
, 4
, 3
5.3.5
Map Descriptor Example 2 - Binary Input (Zone Machine)
A read from the Binary Input Data Array which is shared by a BACNet IP Map Descriptor will return the relay state for the given zone. The Lutron Machine Map Descriptor
regularly polls the eLumen panel to retrieve the value of zone intensity. The value of each BACnet object presenting Binary Output is inactive if the intensity is zero and
active if the intensity is non-zero. Zone numbers range from 0 to 511
BACNet IP Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name
, Data_Type , Object_ID , Length , Relinquish_Default
SMD00_BI
, Binary_Input
, 0
, Passive
, Virtual_BCU_11 , BI
, 1
, 512
, 0
Lutron Machine Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Grafik_Command , Zone , Length
Zone_int_0
, Binary_Input
, 0
, Arco
, LUT_GRF6_0 , Zone_Intensity
, 0
, 512