FS-8700-97 Lutron Machine Manual
Page 14 of 24
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
5.3.8
Map Descriptor Example 5 - Analog Output 1 (Zone Machine)
A write to the Analog Output Data Array which is shared by a BACNet IP Map Descriptor will command a zone on the Lutron eLumen panel to the written intensity.
Intensities are written as a percentage value (0 to 100%).
BACNet IP Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name
, Data_Type , Object_ID , Length , Relinquish_Default
SMD000_AO
, Analog_Output
, 0
, Passive
, Virtual_BCU_11 , AO
, 1
, 512
, 0
Lutron Machine Map Descriptor
// Client Side Map Descriptors
Map_Descriptors
Map_Descriptor_Name , Data_Array_Name , Data_Array_Offset , Function , Node_Name , Grafik_Command , Zone , DA_Lut_Parms
, DA_Lut_Parms_Offset , Length
Fade_to_lvl_0
, Analog_Output
, 0
, Awt
, LUT_GRF6_0 , Fade_Zone
, 0
, Zone_Pars_AO1 , 0
, 512
The zone field must be used to indicate the start zone number that will be associated with the first element of the Data Array specified under Data_Array_Name . Zone
numbers increase with the Length field in association with increasing offset into the Data Array.
Fade and Delay times per zone must be preloaded into the Data Array specified under “DA_Lut_Parms”:
Analog Output1 Settings Setup
All values are in decimal ( 0 - 65535 )
Fade time in even locations, Delay time in uneven locations
Fill in time values under Preload_Data_Value