McQuay Micro Tech Open Protocol Driver Manual
Page 31 of 43
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
4.
Start McQuay Open Protocol Monitoring Software
5.
Enter the User Name as “McQuay” and the password as ”SGC”
6.
Once in the main menu, hit ‘F7’ to enter Advanced Features
7.
Hit ‘F1’ to enter Read/Write Memory
8.
Enter “b00.00” to change the Box Address (Node_HI and Node_LO) to “00”
9.
Enter “w0A11 C1” to write C1 to memory address 0A11. This will set up the comm port configuration
with Port A as TTY and Port B as Master
10.
Test if the wiring to the daisy chained devices is correct by doing the following:
o
To read from a controller with the rotary hex switches set to “01”, change the box address to
01.00 and enter r0A11
o
If you get a response, then it is wired correctly
o
It is suggested that you read from each daisy chained controller
11.
Shut down the McQuay Open Protocol Monitoring Software
12.
Disconnect unit from the PC
13.
Connect FieldServer to Port A (RS-232)