McQuay Micro Tech Open Protocol Driver Manual
Page 22 of 43
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262 2299
Fax
: (408) 262 2269
Toll Free
: (888) 509 1970
7.2
Server Side Node Parameters
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for node
Up to 32 alphanumeric characters
Protocol
Specify protocol used
MCQ, McQuay
Port*
Specify which port the device is connected
to the FieldServer. This parameter is
optional for Server side nodes. The reason
is that when a poll is received on any port
an attempt will be made to match it
against
any
Map
Descriptor/node
irrespective of the port. If emulating more
than one Node with the same address,
however, the Nodes must be linked to
specific ports.
P1-P8, R1-R2
4
PLC_Type
This parameter has no meaning for a
Server but it must be specified to allow the
driver to complete its configuration file
validation.
200CFC, 100CFC, 050RPC, 001ASC, 000SCU, Type-
Unknown
Password*
This parameter is ignored for a Server.
Although every poll contains a password,
this driver does no password validation
when configured as a Server.
Ascii characters only.
Node_Hi
Specify the rotary Hi address switch
setting of the Mcquay controller
0
to F
Node_Lo
Specify the rotary Lo address switch
setting of the Mcquay controller
0
to F
Example
// Server Side Nodes
Nodes
Node_Name , Node_Hi , Node_Lo , Protocol , PLC_Type , Password
Node_A
, 3
, B
, McQuay , 200CFC
, 85760430
7.3
Server Side Map Descriptors
7.3.1
FieldServer Specific Map Descriptor Parameters
Column Title
Function
Legal Values
Map_Descriptor_Name Name of this Map Descriptor
Up to 32 alphanumeric characters
4
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.