FS-8700-74 Veeder Root Driver Manual
Page 9 of 33
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-9042
Toll_Free
: 888-509-1970
4.4.2.
Driver Specific Map Descriptor Parameters
Column
Title
Function
Legal Values
Node_Name Name of Node to fetch data from
One of the node names
specified in “Client Node
Descriptor” above
Data_Type Data
type
System, Tank, Liquid Sensor,
Vapor Sensor, Input,
Volumetric Line, Groundwater
Sensor, Type-B Sensor,
Universal Sensor, Auto-Dial,
Mech. Dispenser, Elec.
Dispenser, Product, Press.
Line, External, WPLLD
*Address
¥
The address is used to specify the
Tank/Sensor/Input /Relay … Number to
be used in the poll. For some data
types the address has no meaning and
should be set to 1.
Veeder-Root Tanks / Sensors … are
numbered from 1. The maximum tank
number is 12 and the maximum sensor
number if 64.
When zero is used as the value of the
address then (in most cases) the driver
polls for all Tanks/ Sensors belonging
to that data type. This is discussed in
the Advanced Topics Section.
0, 1, 2, 3…
Length
¥
Length of Map Descriptor
The length is used to tell the driver how
many elements of the Data Array are
under the control of the Map Descriptor.
This is important because the driver
uses the length to, for example, clear
Data Array elements when a
Tank/Sensor has no alarms.
1 - 1000
4.4.3. Timing
Parameters
Column Title
Function
Legal Values
Scan_Interval
Rate at which data is polled
>0.1s
¥
See Appendix A.1 for Data Type, Address and Length Limitations.