Appendix C.6. Advanced Example 6 – System Revision Level Report II
This example reads additional System Revision Level data from the Veeder-Root Panel. The result is stored in ascii using up to
100 consecutive array elements. Use an array whose format is BYTE or STRING for this function. The notes below explain how the
data should be interpreted.
i90500YYMMDDHHmmSOFTWARE# 346abb-Tvv-rrrCREATED - YY.MM.DD.HH.mmnnAABBCCDDEEFFGGHHIIJJS-MODULE# nnnnnn-vvv-r
YYMMDDHHmm - Current Date and Time
346 - Software Base number (fixed)
a – Platform
(0 = Standard CPU, PLLD only 1 = Enhanced CPU 2 = (Unused) 3 = Enhanced CPU 16 Tank 4 = Standard CPU without PLLD & WPLLD 5 = Standard CPU,
WPLLD only )
bb - Version level (egg version "15")
T - Software Type (1 = "Real" 2 = "Demo" 3 = "IFSF")
vv - Language
rrr - Revision level (e.g. revision "AX1")
YY.MM.DD.HH.mm - Date and time of software creation
nn - number of 2 byte values to follow (Hex)
AA - PERIODIC IN-TANK TESTS (00 = DISABLE, 01 = ENABLE)
BB - ANNUAL IN-TANK TESTS (00 = DISABLE, 01 = ENABLE)
CC - CSLD (00 = DISABLE, 01 = ENABLE)
DD - BIR (00 = DISABLE, 01 = ENABLE)
EE - FUEL MANAGER (00 = DISABLE, 01 = ENABLE)
FF - PRECISION PLLD (00 = DISABLE, 01 = ENABLE)
GG - TANKER LOAD (00 = DISABLE, 01 = ENABLE)
HH - 0.2 GPH PLLD (00 = DISABLE, 01 = ENABLE)
II - PRECISION PLLD ON DEMAND (00 = DISABLE, 01 = ENABLE)
JJ - SPECIAL 3-TANK/LINE CONSOLE (00 = DISABLE, 01 = ENABLE)
nnnnnn-vvv-r - SEM Info 3 parts, if none "NO SOFTWARE MODULE"
nnnnnn - SEM number (ASCII text string)
vvv - SEM Software version number (ASCII text string)
r - SEM Software revision level (ASCII text string)
.
Map_Descriptor_Name, Data_Array_Name,
Data_Array_Offset,
Scan_interval,
Function,
node_name,
Address,
Length,
Veed_Function,
Data_Type
System1poll_1 ,
DA_REVISION2 ,
0 ,,
10.0s ,
rdbc ,
Node_A ,
1 ,
100 ,
0x905 ,
Misc.