Error
Action Required
*VRoot:#13 Err. Device
Rejected message.
Md=<%s>
This message is generated the first time that the Error Statistic
‘Function Error’ is produced. This error can arise in several
ways. The firmware version of the Veeder-Root device may not
support the poll generated by the Map Descriptor. The Veeder-
Root device may not have the tank/sensor/device specified or it
may arise if the message received by the Veeder-Root device is
corrupted. If there are a significant number of these errors then
use Appendix A.2 to determine if the firmware supports the poll.
You can also check the devices configured against the address
specified in the Map Descriptor.
*VRoot:#16 Err. Array too
short to store. Md=<%s>
Rqd=%d
When this error is produced incoming data is being discarded
and alarm or other data will not be updated. There are a few
variations on this message. Some do not report the Rqd length.
This message is produced as a run-time error. It may arise from a
configuration error that has not been corrected. Check for Error
#7 messages. If there are any correct the errors by editing the
CSV file. Then reset the FieldServer. If the driver is still
producing error 16 then you should report this to FieldServer
support. Provide a copy of your configuration file and a port log
to assist in the diagnosis of this error.
*VRoot:#17 Err. Array too
short to store. Md= <%s>
ByteArray
This error is similar to #16 except that it applies to the array
named in the DA_Byte_Name parameter for the Map Descriptor.
*VRoot:#18 Err. Array too
short to store. Md= <%s>
Float Array
This error is similar to #16 except that it applies to the array
named in the DA_Float_Name parameter for the Map Descriptor.
VRoot:#19 Err. Cant
process msg type= %x
You cannot take any corrective action to eliminate this error.
Report the message to FieldServer support. It will assist in the
diagnosis of the error if you can take a port log and provide a
copy of your CSV file.
*VRoot:#20 FYI. Incoming
data is being abandoned.
Func= %x DT= <%s>
Addr=%d
This message is a warning. It indicates that a response to a poll
contains data for which a Map Descriptor cannot be found to
store the data. For example: The response to poll for System
Status returns an alarm for Liquid Sensor #3 but you have not
defined a Map Descriptor for Liquid sensor #3. You may be able
to use the Data Type and the Address to determine what kind of
Map Descriptor is required. If, however, you are satisfied that you
have Map Descriptors for the data of interest to you then you may
safely ignore this message.
*VRoot:#21 Err. Md=<%s>
not bound to a port. Can’t
be used.
§
Read the notes for Error #4 to see how to correct this problem.
Vroot:#22 FYI. Config
reported zero modules.
You may ignore this message. The Veeder-Root device reported
zero configured modules in response to a configuration enquiry.
*VROOT:#23 Err. Address=
0 invalid for this command.
Set the address to a positive number corresponding to the
tank/sensor/input/device whose data you are polling for.
§
This is a configuration error which can be eliminated by correcting an error in the CSV file and resetting
the FieldServer.