FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 9 of 21
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
: www.fieldserver.com
Tel
: (408) 262-2299
Fax
: (408) 262-2269
Toll Free
: (888) 509-1970
5.2
Client Side Connection Parameters
Section Title
Connections
Column
Title
Function
Legal Values
Port
Specify which port the device is connected to the
FieldServer
P1-P8
1
Protocol
Specify protocol used
nfs2-nca; nca2; nfs2-3030
Baud*
Specify baud rate
CRT Port
4800;
9600
; 19200; 38400; 57600; (Vendor
limitation)
Printer Port
9600
(Vendor limitation)
Parity*
Specify parity
None
(Vendor limitation)
Data_Bits*
Specify data bits
8
(Vendor limitation)
Stop_Bits*
Specify stop bits
1
(Vendor limitation)
Example
// Client Side Connections
Connections
Port , Protocol , Baud , Stop_Bits , Parity
P8
, nfs2-nca , 9600 , 1
, None
5.3
Client Side Node Parameters
Section Title
Nodes
Column Title
Function
Legal Values
Node_Name
Provide name for Node
Up to 32 alphanumeric characters
Node_ID
Station address of any physical Node on
network
1-240. Set unique Id for standalone Notifer-
3030 Panel
Protocol
Specify protocol used
nfs2-nca or nca2 ; nfs2-3030
Port
Specify which port the device is connected
to the FieldServer
P1-P8
Example
// Client Side Nodes
Nodes
Node_Name , Node_ID , Protocol , Port
Panel_1
, 2
, nfs2-nca ,P8
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.