Note 1:mode: 2' bit definitions:
Note 2: hold: 2' bit definitions:
0X01
Unit is in centigrade mode
0X01
needed cooling is inhibited
0X02
RFU , always 1
0X02
needed heatingg is inhibited
0X04
RFU , always 1
0X04
needed humidification is inhibited
0X08
Unit is dehumidifying
0X08
needed dehumidification is inhibited
0X10
Unit is humidifying
0X10
not used
0X20
Energy save is active
0X20
not used
0X40
not used
0X40
Network"standby" inhibit is active
0X80
not used
0X80
Network"off" inhibit is active
Note 2: errors: 7*2' bit definitions:
00
Manual override:check bypass switches
errors[0], bit 0x01
01
water detected under floor
errors[0], bit 0x02
02
No air flow, check belt and motor
errors[0], bit 0x04
03
dirty filter: check filter
errors[0], bit 0x08
04
Humidifier problem: check water pressure
errors[0], bit 0x10
05
Low voltage warning
errors[0], bit 0x20
06
Firestat alarm, unit shutdown
errors[0], bit 0x40
07
compressor short cycle
errors[0], bit 0x80
08
power problem or unit restart
errors[1], bit 0x01
09
humidity sensor problem
errors[1], bit 0x02
10
temperature sensor problem
errors[1], bit 0x04
11
schedule maintenance due
errors[1], bit 0x08
12
high presure C1: manual reset
errors[1], bit 0x10
13
low presure C1: auto reset
errors[1], bit 0x20
14
high presure C2: manual reset
errors[1], bit 0x40
15
low presure C2: auto reset
errors[1], bit 0x80
16
smoke detector: unit shutdown
errors[2], bit 0x01
17
No water flow :check pump
errors[2], bit 0x02
18
Discharge temperature sensor problem
errors[2], bit 0x04
19
High Temperature warning
errors[2], bit 0x08
20
Low temperature warning
errors[2], bit 0x10
21
High humidity warning
errors[2], bit 0x20
22
low humidity warning
errors[2], bit 0x40
23
Fan motor overload: check motor amperage
errors[2], bit 0x80
24
Local alarm 1: see tag inside door
errors[3], bit 0x01
25
Local alarm 2: see tag inside door
errors[3], bit 0x02
26
Local alarm 3: see tag inside door
errors[3], bit 0x04
27
Local alarm 4: see tag inside door
errors[3], bit 0x08
28
Standby Pump on: check primary pump
errors[3], bit 0x10
29
UPS power on: check primary power
errors[3], bit 0x20
30
Custom message on optional input 1
errors[3], bit 0x40
31
Custom message on optional input 2
errors[3], bit 0x80
32
Custom message on optional input 3
errors[4], bit 0x01
33
Custom message on optional input 4
errors[4], bit 0x02
34
Humidification inhibited
errors[4], bit 0x04
35
Reheat inhibited
errors[4], bit 0x08
36
Reheat and humidification inhibited
errors[4], bit 0x10
37
Discharge air temperature limit
errors[4], bit 0x20
38
Reheat mode during dehumidication
errors[4], bit 0x40
39
Manual override:check bypass switches
errors[4], bit 0x80
40
High condensate water level
errors[5], bit 0x01