FS-8700-49_Data_Aire_DAP
Page 15 of 48
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.FieldServer.com
Tel
: (408) 262-2299
Fax
: (408) 262-2269
Toll_Free
: 888-509-1970
Array
Location
Method
Num
Elements
Data Field
2 3 4 5 6 7 8 9 14 15 Message Type
498
1
1
loc_h_deadband
X
X X
Dap-Menu
499
1
1
loc_h_setpt
X
X X
Dap-Menu
500
2
1
loc_t_dband
X
X X
Dap-Menu
501
2
1
loc_t_setpt
X
X X
Dap-Menu
502
1
1
lo_cal
X
X X
Dap-Menu
503
1
1
lo_h_lim
X
X X
Dap-Menu
504
2
1
lo_t_lim
X
X X
Dap-Menu
505
1
1
main_int
X
X X
Dap-Menu
506
1
1
passwd_a
X
X X
Dap-Menu
507
1
1
passwd_b
X
X X
Dap-Menu
508
1
1
rst_mode
X
X X
Dap-Menu
509
1
1
s_delay
X
X X
Dap-Menu
510
2
1
t_calib
X
X X
Dap-Menu
511
1
1
voice
X
X X
Dap-Menu
512
1
1
vvrg
X
X X
Dap-Menu
513
1
1
cat1
X
X X
Dap-Menu
514
1
1
cat2
X
X X
Dap-Menu
515
1
1
cat3
X
X X
Dap-Menu
516
2
1
d_calib
X
X X
Dap-Menu
517
2
1
lo_d_lim
X
X X
Dap-Menu
518
1
1
ptc
X
X X
Dap-Menu
519
2
1
supplyT
x x
x
Chiller-Stat
520
2
1
returnT
x x
x
Chiller-Stat
521
4
1
coolOn1
x x
x
Chiller-Stat
522
4
2
coolOn2
x x
x
Chiller-Stat
523
4
2
coolOn3
x x
x
Chiller-Stat
524
2
1
valvePct
x x
x
Chiller-Stat
525
4
1
pumpsOn
x x
x
Chiller-Stat
526
4
1
condOn
x x
x
Chiller-Stat
527
4
1
modFail
x x
x
Chiller-Stat
528
2
1
hiSupT
x x
x
Chiller-Stat
529
2
1
loSupT
x x
x
Chiller-Stat
530
2
1
hiRetT
x x
x
Chiller-Stat
531
2
1
loRetT
x x
x
Chiller-Stat
532
1
1
csUtilPct1
x x
x
Chiller-Stat
533
1
1
csUtilPct2
x x
x
Chiller-Stat
534
1
1
csUtilPct3
x x
x
Chiller-Stat
535
1
1
valveUtilPct
x x
x
Chiller-Stat
536
3
48
Errors - see Appendix E.4
for more information
x x
x
Chiller-Stat
584
1
1
mode
x x
x
Chiller-Stat
585
6
11
runtimes
x x
x
Chiller-Xtra
596
3
80
errold
x x
x
Chiller-Xtra
676
6
10
errage
x x
x
Chiller-Xtra