FS-8700-49_Data_Aire_DAP
Page 20 of 48
FieldServer Technologies
1991 Tarob Court Milpitas, California 95035 USA
Web
:www.FieldServer.com
Tel
: (408) 262-2299
Fax
: (408) 262-2269
Toll_Free
: 888-509-1970
FieldServer
Array
Location
FieldServer Data
Field
Point Description
Message
Type
D/A Control Panel
Type
474
adj_rate
Adjustment rate
DAP Menu
DAP049,048,046
478
alrm_delay_1
optional alarm 1 delay
setting
DAP Menu
DAP049,048,046
479
alrm_delay_2
optional alarm 2 delay
setting
DAP Menu
DAP049,048,046
480
alrm_delay_3
optional alarm 3 delay
setting
DAP Menu
DAP049,048,046
481
alrm_enable_1
Enable optional alarm 1
for alarm relay
DAP Menu
DAP049,048,046
482
alrm_enable_2
Enable optional alarm 2
for alarm relay
DAP Menu
DAP049,048,046
483
alrm_enable_3
Enable optional alarm 3
for alarm relay
DAP Menu
DAP049,048,046
484
alrm_select_1
Select alarm message for
Optional alarm input 1
DAP Menu
DAP049,048,046
485
alrm_select_2
Select alarm message for
Optional alarm input 2
DAP Menu
DAP049,048,046
486
alrm_select_3
Select alarm message for
Optional alarm input 3
DAP Menu
DAP049,048,046
487
Chilled_water
Chilled water Valve
configuration
DAP Menu
DAP049,048,046
488
Compressor_config
Compressor configuration
DAP Menu
DAP049,048,046
489
c_mode
Unit in Centigrade
temperature mode?
DAP Menu
DAP049,048,046
490
fire_lim
Firestat temperature
setting
DAP Menu
DAP049,048,046
491
heat_strip_config
Heating configuration
DAP Menu
DAP049,048,046
492
hi_cal
A to D high limit setting
DAP Menu
DAP049,048,046
493
hi_h_limit
High humidity alarm limit
setting
DAP Menu
DAP049,048,046
494
hi_t_lim
High temperature alarm
limit setting
DAP Menu
DAP049,048,046
495
humid_config
Humidifer configuration
DAP Menu
DAP049,048,046
496
h_calib
Humidity calibration offset
DAP Menu
DAP049,048,046
497
lead_lag
Compressor lead/lag
setting
DAP Menu
DAP049,048,046
498
loc_h_ddband
humidity deadband setting
DAP Menu
DAP049,048,046
499
loc_h_setpt
Humidity setpoint
DAP Menu
DAP049,048,046
500
loc_t_dband
Temperature deadband
setting
DAP Menu
DAP049,048,046
501
loc_t_setpt
Temperature setpoint
DAP Menu
DAP049,048,046
502
lo_cal
A to D low limit setting
DAP Menu
DAP049,048,046
503
lo_h_lim
Low humidity alarm limit
setting
DAP Menu
DAP049,048,046
504
lo_t_lim
Low temperature alarm
limit setting
DAP Menu
DAP049,048,046
505
main_int
Maintenance schedule
setting
DAP Menu
DAP049,048,046
506
passwd_a
Password A setting
DAP Menu
DAP049,048,046
507
passwd_b
Password B setting
DAP Menu
DAP049,048,046