Maintenance & repair 

 

Ordinary Problems 

 

If the UPS is operated with normal method, the panel will display the 

current working status. The following are ordinary UPS failure problematics : 

Problem 1: The UPS will not switch to electric supply status after turning 

on.   

Solution      : Check whether the power cord is well connected with the 

electricity network socket; whether the input AC fuse has burned out. (There 
is one spare fuse in the input fuse socket, please use fuse of same 
specifications). 

Problem 2: Unplug the input power cord after it is turned on, but the 

UPS cannot switch to Inverter supply status.   

Solution    : The battery voltage is too low, output is overloaded, or output 

short circuit; please charge the battery or change it, check whether the 
output is overloaded and reduce the load, or whether the output loop is 
short-circuited. 

 
 
 

Maintenance 

 

If the UPS is not being used for a long time ,then it should be charged 8

10 

hours every three month. If possible, please discharge the battery with the 
computer or 100W light bulb for 1

3 minutes. The purpose of discharging is 

to activate the battery. The battery is only allowed for long-time storage after 
it  is  fully  charged;  or  the  battery  capacity  will  reduce  due  to  performance 
erosion  after  long-time  stall.  The  long-time  under  voltage  (or  even  zero 
voltage) due to battery self-discharging will “kill” the battery. 

 
Regularly check the power supply and input and output lines of all 

equipments, so as to guarantee the reliability of peripheral lines. 

 

Содержание Lupus 1000

Страница 1: ...500 700 1000 1600VA User Manual ...

Страница 2: ...ry Problems 7 Maintenance 7 Replacing the Battery 8 Safety precautions 9 Technical specifications 10 Terms of warranty 11 List of of service centers 12 Please read this user manual carefully before operation Please keep this manual handy for future reference The printer socket is applicable for laser printer No output if mains is down It is prohibited to connect loads such as electric fan electric...

Страница 3: ...an automatically monitor the input surge decline break abnormal frequency output load status and battery status etc thus providing the load with comprehensive protections Complete in functions Complete Protection Function With protections for input over voltage under voltage surge output over voltage over loading short circuit over charged battery and under voltage has greatly improved the reliabi...

Страница 4: ...of electricity network When the mains resumes to normal status UPS will start automatically and the battery charger will start charging the battery as well The battery will be charged fully within 8 to 10 hours of charging Installation use Panel and backboard of UPS Figure 1 Panel and backboard schematic diagram of UPS LED models RS232 RS232 OUT IN For TEL DSL FAX Modem DC INPUT Surge Protection A...

Страница 5: ... core power cord P N G the output is a three core standard IEC socket and the UPS case is connected with ground wire Please make sure the ground wire is well connected 4 Plug the UPS input power cord into the mains socket and plug the other end into the UPS input socket Please make sure the neutral wire and live wire are in accordance with national standards and the ground wire should be well conn...

Страница 6: ...lly charged AC NORMAL On OUTPUT On Displays the full battery bar Silent Electric Supply is down or abnormal UPS is supplying power from the Inverter to the load BATTERY On OUTPUT On The reduction of lighted battery capacity indication led means that the battery is discharging Slow Beeping Every 3 Seconds And beeps every 10 seconds after 10 beeps UPS battery is fully discharged Please save data and...

Страница 7: ...t is overloaded or output short circuit please charge the battery or change it check whether the output is overloaded and reduce the load or whether the output loop is short circuited Maintenance If the UPS is not being used for a long time then it should be charged 8 10 hours every three month If possible please discharge the battery with the computer or 100W light bulb for 1 3 minutes The purpos...

Страница 8: ...AC input and output power cords 2 Unscrew the 7 screws on the cover with a cross screwdriver 3 Carefully put the UPS upside down and unscrew the 3 screws on the battery cover 4 Carefully take out the battery and put in new battery 12V 7AH maintenance free battery 5 Lock the battery cover and top cover Replacing the battery in the other models require after opening the cover removing the clamps fro...

Страница 9: ...while it is on as it may lead to an electric shock 3 The UPS should be placed at least 25 cm from the monitor so as to prevent interference 4 It is absolutely prohibited to place cups or other liquid containers on the top this machine so as to avoid internal short circuit that may lead to dangers such as electric shock etc 5 Do not store or use this machine in the following surrounds Sites with fl...

Страница 10: ...ed voltage Start inverter when the input voltage 275VAC Deep discharge batteries UPS off when the battery voltage drops below the set level Turn on the battery indicator Overload or shorting Immediately for overloads 150 Fast for a compact battery Switching time 6ms Panel Indicators LCD display Network operation battery operation overload battery status battery discharged failure Sound alarm Opera...

Страница 11: ...ed repairs alterations or design changes Activities provided in the manual to which the user must own and at their own expense such as installation commissioning verification activities replacement mains fuse Proper packaging protection equipment to the site should be sent to the sender It is recommended that the unit was shipped in the original containers equipped with protective pads fitted to t...

Страница 12: ...12 List of of service centers Fideltronik Inigo Sp z o o Obroncow 25 03 933 Warsaw tel fax 48 022 871 43 36 inigo fideltronikinigo com www fideltronikinigo com ...

Отзывы: