6.16.4 Auto Reservoir Refill Function
The constant dispensing control logic comes with auto reservoir refill & output
logic. Refer to below diagram illustration diagram for auto reservoir refill
sequence.
6.16.5 Auto Reservoir Refill Sequence Description
Seq.
Point
Description
1
L
0
I
0
Reservoir refill in process. Relay 1 in action.
2
I
0
a. Reservoir refill completed.
b. Relay 1 stops action.
3
I
0
J
0
c.
In case
[FUNC]
key is pressed or had been
previously pressed (at reservoir weight value less
than rEF L).
d.
Time delay as set forth in Delay 1.
4
J
0
Dispensing sequence starts.
5
J
0
K
Weight of material in reservoir decreased after one or
more dispensing sequence.