2 The PDP
Version A
2-3
Figure 2-2
Structure of the PDP (rear)
2.3
Power Terminals
2.3.1
Power Supply Connector Posts
The main and branch power supply connector posts are located on the rear panel
of the PDP, as illustrated in Figure 2-3.
Main power supply connector posts: Located on the right side of the PDP rear
panel, are used to connect the external power cables and input two channels
of DC -48V power into the PDP.
Branch power supply connector posts: Located on the left side of PDP rear
panel, are used to connect subrack power cables and output PDP’s power rail
to the subracks.
Caution:
P1 and P2 can be used together to provide redundant power rails for
each subrack, or used separately to provide a single non-redundant
power rail for each subrack.
If the equipment room provides only the single power rail, but the
AN5116-06B requires redundant power rails or 6 branch power rails,
users can use shorting plugs to short circuit -48V1 and -48V2; GND1
and GND2 of the main power supply connector posts.