FUNCTIONING WITH REMOTE CONTROL ENCRONO OT1 or OT2
Ele
k
tra..
N
016
, can be connected by
means of its board and an additional module
to install on a prearranged part, to a
compatible remote control device
Opentherm®, like Encrono OT1 or OT2. This
can be obtained by means of the interface
board (additional module). When the board
finds the connection with the remote control,
on the LCD display appears the symbol
M
.
The compatible remote control OpenTherm
becomes the master of the entire system, therefore almost all the functionalities, as the
setting of heating and hot sanitary water set-point or the control of system status, are
directly executable by it, in relation with the kind of application on which the board is used.
By means of the remote control it is possible to restore (RESET) the system from the non-
volatile lock status.
The communication between the remote control and the electronic board fitted with D.E.S.
system can be interrupted in the following ways: Interruption of the connection between
remote control and board: in this case, after 1 minute, the board starts to work in local
mode.
Noise on communication cable between remote control and board: in this case it is
possible that remote control and board do not manage to communicate (wrong data
interpretation), therefore, after a certain lapse appears the related error signal. If the noise
on the communication cable ends, the dialog between remote control and the board is
automatically restored and the malfunction disappears.
TRANSPARENT PARAMETERS
This function is available only with the use of remote control OT2. The digital electronic
PCB is equipped with 10 parameters adjustable by the installer, in order to set the
functioning of the system in conformity to the final application. The parameters have the
same meaning of the ones described in the table “parameters”.