background image

9

CHOICE OF THE OPERATION MODE (Winter/Summer) 

Pressing the key MODE (J4), i twill be chosen the mode of operation, wintry or summery. 

Pressing repeatedly each time for at least 5 seconds, you switch from WINTER to 

SUMMER or from SUMMER to WINTER then. When the device will be in WINTER mode,

on the display will appear the Symbol 

C

 

(snow). When the device will be in SUMMER

B

 

(sun). 

TEMPERATURE VARIATION OF THE HEATING CIRCUIT 

When the apparatus has been set with the snow symbol (

C

) for the wintry functioning, you 

can change the maximum temperature of heating circuit pressing one of the two keys with the radiator

symbol located on the left of the display (

+

I

 and 

I

 keys

). The key with the symbol 

+

I

 (J2),

increases the temperature, and the key with the symbol 

-

I

 (J3) decreases the temperature.

 

ON-OFF KEY (Display symbols)

The ON/OFF (J7) key, in addition to put the boiler

in stand-by mode, allows to reset (unlock) the apparatus

in case of high temperature lock. If the lock would

be caused by lack of water pressure alarm, the recovery

will be automatic after that the hydric pressure will

be restored at the minimum operating level (0,08 MPa - 0,8 bar) by means of the operating

and the closure of the charging tap placed under the boiler (black handle). The display has

several symbols, signaling in addition to operation modes, also the various alarm or system displays: 

Symbol 

Meaning 

Malfunction 

Request of burner switch-on 

Heating request 

Parameter menu activated 

Anti-freeze request activated 

Winter mode 

Summer mode 

OFF mode 

Level of 

modulation 

Indicates the instantaneous power of the boiler by 0 to 100% 

mode, on the display will appear the Symbol 

 

Содержание Elektra 18 kW N 016 TROLLEY

Страница 1: ...lley series USER AND MAINTENANCE MANUAL EQUIPMENT CONFORM TO EC DIRECTIVE 2006 95 EC And built in compliance with IEC 60335 2 21 2012 IEC 60335 1 2010 EN 60335 2 21 2003 A1 2005 A2 2008 EN 60335 1 2012 EN 62233 2008 Power supply 400 V 50 Hz N three phase power ...

Страница 2: ......

Страница 3: ...as to manage both comfort and economy functioning in order to reduce power consumption when the device is not used at the maximum capacity or demand the appliance is fully adjustable both in water temperature of the heating system with the possibility to choice of system at high and low temperature for the underfloor systems and in the domestic hot water temperature The assembly of the components ...

Страница 4: ...E NETWORK WITH A DISTANCE CONTACT OPENING ALLOWING THE COMPLETE DISCONNECT THE CONDITIONS OF OVERVOLTAGE CATEGORY III UNDER THE RULES OF INSTALLATION IF THE POWER CABLE IS DAMAGED IT MUST BE REPLACED BY THE MANUFACTURER OR THE TECHNICAL ASSISTANCE SERVICE OR OTHERWISE BY A PERSON WITH SIMILAR QUALIFICATION IN ORDER TO PREVENT ANY RISK WATER CAN DRIP FROM EXHAUST DEVICE AGAINST OVERPRESSURE AND THE...

Страница 5: ...evels but the same overall dimensions Elektra 18 kW N 016 TROLLEY 18 kW maximum electrical output Appliance dimension Packaging dimensions L Width 400 mm Width 440 mm H Height 875 mm Height 940 mm P Depth 300 mm Depth 390 mm Weight 39 kg Weight 41 kg L P H ...

Страница 6: ...y valve 0 3 MPa 3 bar F RC Manual filling tap restoring water pressure The unit is expected to be connected in a continuous manner to the water mains without the use of a set of junctions Bottom view under the boiler Electrical supply VSR It must be removed by opening knock out M R 165 40 95 80 120 R M Electrical supply ...

Страница 7: ...ating of 18 kW obtained by n 3 Resistance group n 3 da 3x2 kW Maximum head available at the pump of 7 m c a Expansion vessel capacity of 10 liters Safety valve of heating circuit of 0 3 MPa 3 bar Maximum heating operating pressure 0 25 MPa 2 5 bar Minimum operating pressure in the heating circuit 0 06 MPa 0 6 bar Maximum limit of thermal safety heating circuit boiler body 100 C ...

Страница 8: ...re for the system is between 1 and 1 5 bar More then 1 5 bar you can have a maximum pressure of the 2 bar maximum expansion of the system during the rise in temperature More than 2 bar pressure the system is not in the range of operation and the mechanical safety valve preset to 3 bar can start to lose water to access the valves remove the knockout openings at the valves see page 2 hydraulic insta...

Страница 9: ... setpoint or room temperature J7 J6 J5 J4 J3 J2 TURNING ON THE BOILER The boiler is switched on by means of the general switch located on the left of the display in the instrument panel of the boiler Pressing the switch upward to the ON position it will light in the presence of three phase supply 400 V 50 Hz Then it shall be pressed the ON OFF J7 on the keypad to switch the power from stand by to ...

Страница 10: ...the key with the symbol I J3 decreases the temperature ON OFF KEY Display symbols The ON OFF J7 key in addition to put the boiler in stand by mode allows to reset unlock the apparatus in case of high temperature lock If the lock would be caused by lack of water pressure alarm the recovery will be automatic after that the hydric pressure will be restored at the minimum operating level 0 08 MPa 0 8 ...

Страница 11: ...ch CC Boiler body VSR Safety valve heating circuit x0 3 MPa 3 bar S Thermowell for immersion sensor VE Expansion vessel heating circuit RC Boiler resistance 6 kW R Hydraulic connection inlet heating circuit AF Cold Water M Hydraulic connection outlet heating circuit T Termometer rsc Drain valve of boiler body VIM Manual interception ball valve GC Automatic loading group T T VIM AF VIM GC ...

Страница 12: ...10 11 51 51 50 49 48 47 46 45 44 43 4241 40 38 37 36 55 56 54 J11 Interface 961 O JP7 JP8 JP9 JP10 0 1 39 1 2 3 1 2 3 4 5 6 7 J14 J12 J11 J5 J6 N RT G3 G2 G1 G4 OUT 230 240V 53 OT PE F E white yellow red blue brown black black black brown brown brown blue brown red b l ue red black G5 brown ST black TT grey G5B green ...

Страница 13: ...ontact TS on contactor of power C NO cTS Control gate triac n 1 4 KW power G1 Control gate triac n 2 2 KW power G2 Control gate triac n 3 4 KW power G3 Control gate triac n 4 2 KW power G4 Control gate triac n 5 4 KW power G5 Control gate triac n 5B 2 KW power G5B Delivery heating probe ntc sensor SM External probe sensor SE Water pressure switch PSA Safety thermostat TS Room thermostat terminal p...

Страница 14: ...13 TRIAC Connection scheme ...

Страница 15: ...start up P 1 0 0 1 Building coefficient of dispersion P 2 35 5 35 C Sanitary post circulation P 3 15 1 180 sec Heating post circulation P 4 30 1 180 sec Heating exchanger circulation starting P 5 0 0 240 sec Min ignition temperature circulator P 6 30 0 50 C Delivery differential of sanitary P 7 15 0 20 C Type kettle present P 8 0 0 Internal probe 1 External thermostat 2 External probe Type of sens...

Страница 16: ...ain exchanger are turned on all or partially The actuaction of each control is reduced to a lapse of 4 seconds Higher is the required power more the control will remain operative in this lapse The power in heating or during a sanitary request is calculated by PID algorithm Please see in the pictures below two examples related to 40 and 60 of total power 12 kW G1 G2 G3 G5 G5B 4 s G1 G2 G3 G5 G5B 4 ...

Страница 17: ...setpoint chased by the heating delivery probe will be calculated as follows Tch C Troom C Text C dc 10 Troom C Tch heating setpoint calculated by the system Troom ambient temperature set by the user Text outside temperature measured by the probe dc dispersion coefficient of the building can be set by parameter P2 28 33 38 43 48 53 58 63 68 73 20 15 10 5 0 5 10 15 20 35 30 25 20 15 10 8 5 Text C Tc...

Страница 18: ...ists of a hydraulic system a wet rotor motor with permanent magnet rotor and an electronic control module with integrated frequency converter The control module contains a control button the pump is also equipped with an LED indicator to display the operating status of the pump Functions All functions can be set activated or deactivated using the command button Variable pressure difference p v The...

Страница 19: ... of the 10 minutes the pump stops and automatically switches to the p c max setting mode 18 Then you need to set the adjustment mode and prevalence if the pump does not have to continue to operate in p c max mode NOTE The vent function removes the air accumulated in the pump rotor compartment This function does not affect the heating system Setting the adjustment mode By turning the control button...

Страница 20: ...er value decrease H J6 Parameter value increase ON OFF J7 Exit by parameters menu I J2 Parameter index increase I J3 Parameter index decrease Heating elements status The dashes located in the upper part indicate the heating elements status Every mark is equivalent to the triac reference G1 4 kW G2 2 kW G3 4 kW G4 2 kW G5 4 kW and G5B 2 kW G1 G2 G3 G4 G5 G5B HEAD SCREEN APPLICATION To select the us...

Страница 21: ...ures is below 20 C the number of hours is replaced with the word to indicate that the count is not advanced The modulation bar is displayed at the end of the pre heating phase of the primary exchanger Once the 72 hours of testing have been completed the system automatically modifies the set point to be followed at the value set before starting the test design temperature The display shows that the...

Страница 22: ...ion bar is displayed at the end of the pre heating phase of the primary exchanger At the end of the set time the system stops the power resistors and the system circulator and displays the test end To allow the system to repeat the test simply press the room thermostat or using the ON OFF J7 key switch off and on again At any time the current test can be terminated by opening the room thermostat A...

Страница 23: ...code RESET OF THE APPARATUS RESET To unlock the device press the ON OFF J7 button which also has the Reset function RESET Code Err Meaning F 9 Hardware EEPROM failure F 1 Insufficient system water pressure F 3 Boiler delivery probe error F 8 Safety thermostat block To restore press the ON OFF J7 system ...

Страница 24: ...e lock status The communication between the remote control and the electronic board fitted with D E S system can be interrupted in the following ways Interruption of the connection between remote control and board in this case after 1 minute the board starts to work in local mode Noise on communication cable between remote control and board in this case it is possible that remote control and board...

Страница 25: ...essure of one key two keys activated the backlighting of LCD display Key Function H J5 Disabled in Opentherm mode H J6 Disabled in Opentherm mode ON OFF J7 Unlock error of safety thermostat exit temperature visualization MODE J4 Disabled in Opentherm mode I J2 Disabled in Opentherm mode I J3 Disabled in Opentherm mode CONTROL PANEL IN TEMPERATURE MENU The buttons have the same operation described ...

Страница 26: ...25 SPARE PARTS 3 Particular Upper particular resistance Boiler body resistances 1 2 6 3 5 6 7 10 4 10 15 21 20 23 16 23 11 8 9 11 17 11 14 17 19 15 12 13 18 1 14 16 19 25 26 22 23 13 ...

Страница 27: ... cable connection LCD display Cod P 2095 5 Left side panel of casing Cod P 2030 6 Triac of electric power 40 A 600 V Cod P 2293 7 Return tube heat exchanger pump Cod P 2037 8 Expansion vessel 8 liters N BP 6 kW version Cod P 289 Expansion vessel 10 liters N C BP 12 18 24 kW version Cod P 1846 9 Water pressure switch minimum pressure Cod P 7623 10 Circulator at variable prevalence electronic pump C...

Страница 28: ...ntactor of power for Elektra 12 Cod P 2153 Contactor of power for Elektra 18 Cod P 2104 Contactor of power for Elektra 24 Cod P 2101 22 O ring gasket for 3x2 kW electrical resistance for Elektra Cod P 2078 23 Electrical resistance 3x1 kW Elektra 6 Cod P 7410 Electrical resistance 3x2 kW Elektra 12 18 24 Cod P 2718 24 Drain tap for Elektra boiler tank Cod P 2190 25 Contact safety thermostat 100 C E...

Страница 29: ......

Страница 30: ......

Страница 31: ... L Landucci n 2 B 51100 PISTOIA ITALY Telefono Telephone 39 0573 532812 Telefax Telefax 39 0573 532890 Tipo di apparecchio Type of equipment Caldaia murale elettrica Electric wall boiler Marchio commerciale Trademark dicitura FIAMMA FIAMMA marked Tipo Modello Type Model Vedi Modello su targhetta dati See the model in data code ELEKTRA 6 12 18 24 ELEKTRA 6 12 18 24 Le norme armonizzate o le specifi...

Страница 32: ...ilerparts hotmail co uk www euroboilerparts co uk FIAMMA GIRO s r l Company group Sede legale e stabilimento via L Landucci n 2 B 51100 PISTOIA ITALY Tel 39 0573 532812 Fax 39 0573 532890 E mail fiammaPT fiammagiro it Filiale e stabilimento via P Bettini n 19 37049 VILLA BARTOLOMEA VR ITALY Tel 39 0442 659028 Fax 39 0442 659045 E mail fiammaVR fiammagiro it www fiammagiro com ...

Отзывы: