FIAMM SoNick I&O - 48TL160H rev.0
– July 2013
pag.12
Fig.9
3.5.4 Single battery installation
In case of a single battery installation a data cable could be permanently connected to the
output port in order to access the communication bus, the alarm dry contact and the remote
powering pins
Fig 10
3.5.5 Multiple batteries installation
In case of multiple battery installation, a daisy chain configuration of the data cable is
possible. Output port of one battery should be connected with the input port of the following
battery, as showed in the figure 11. With this configuration all the battery of the chain are
connected to the same communication bus (RS485 or CanBus) and each single battery
have to be named with the software configuration.
Maximum number of batteries that can be connected in the same data chain is 64
with the RS485 or 127 when CanOpen protocol is used.
Fig. 11
RS485
CANBUS
Alarm
dry
contact
Remote
power
on/off
RS485/
CANBUS
Common
alarm dry
contact
Common
remote
power
on/off