MCS-11 REMOTE ENCODER MODEL 2310 AL SPECIFICATIONS
PHYSICAL
height: 1 and 23/32 in. (1U)
width: 19 in.
depth: 11 in.
weight: 5.2 lbs.
POWER REQUIREMENTS
supply voltage: 18 volts to 56 volts, positive or negative ground
supply current: 215 ma @18 volts, no relays activated, no analog option card
475 ma @18 volts, all relays activated, no analog option card
305 ma @18 volts, no relays activated, with analog card installed
570 ma @18 volts, all relays activated, with analog card installed
(note: current draw decreases as voltage increases)
supply fuse: internal 1 Amp 250 Volt 2AG fuse
connections: barrier terminal strip - rear panel
RELAY OUTPUTS
connections: Form-C contacts for all 16 relays are available on a 50-pin female ribbon connector on the
rear panel. Each relay's common connection is internally fused (1 Amp. pico fuse). An additional Form-A
relay output is available to set an external RSS summary point.
current rating: 1 Amp maximum in 24 or 48 volt station service, 0.6 Amp in 120 Volt service
OPTO ISOLATED INPUTS
connections: The 32 inputs are available on a 50-pin female ribbon connector on the rear panel.
input load: 22K Ohm pull-up to station battery (monitored equipment must sink 2ma maximum to station
ground in order to assert alarm). Bi-directional LEDs are used in the optoisolators, so positive or negative
ground systems both work properly.
ANALOG INPUTS (OPTIONAL)
connections: The 16 inputs are available on a DB-25 female connector on the rear panel.
input load: 52K Ohms input resistance to ground for all inputs.