REAL TIME MONITORING
The 2310 AL can be set to monitor and display its alarm input conditions, the status of its control
outputs, and its analog input values. This can aid in field troubleshooting and verify that the 2310
AL is functioning properly.
To start Monitor mode, first select the appropriate COM port (used to communicate with the 2310
AL craft port), then press the
Change Mode
button found on all four of the tabbed pages. The
current mode, either Configuration or Monitor, is always displayed above the button. The program
immediately uploads the current configuration data from the 2310 AL, then switches to Monitor
mode. All configuration functions are disabled in Monitor mode, but you can select any of the
tabbed pages to display the desired RSS or RDS alarm points, RCDI control point statuses, or the
RAS analog input values.
Figure 14. RDS PAGE IN MONITOR MODE
The input readings are refreshed automatically every 1 to 2 seconds and are images of the
appropriate scanners (RSS or RDS, RCDI, & RAS). If an RSS or RDS alarm input is set for a
delay, the input must remain asserted for the complete delay time before it is shown as asserted on
the Monitor page. Asserted alarm points are highlighted in red, status points in yellow.
Press the Change Mode button again to return to Configuration mode.