DCP-10
Page 5/27
3. Panel Operation
The operation panel consists of 3 sections: LCD display indicating measurement parameters, LED
indicator for common failure, and push buttons for Genset and selection of control modes.
The LCD circularly displays different measuring parameters. When failure occurs, LCD displays the
corresponding fault icon. LCD also has a backlight so that the operator can clearly read information day
or night. After pressing any button the backlight will automatically turn off in a certain time.
The LCD display and its control push buttons provide a friendly operation interface for the operator to
conveniently read information and parameter setting.
3.1 Control buttons and LEDs
Function Description
Tag
Scroll Button
Enter into submenu / Modify / confirm modification / scroll menu to
display.
MUTE / LAMP TEST Button
When failure occurs, alarm buzzer sounds. Pressing mute button will
mute the sound. LCD displays mute icon. Press and hold mute button
for 2sec, all LEDs illuminate simultaneously.
AUTO Mode Button / LED
The push button is used for selecting “AUTO mode”. When the
controller is running in AUTO mode, the LED above the push button
illuminated. The activation and deactivation of the “remote start signal
input” controls the starting and stopping of the Genset.
MAN Mode Button / LED
The push button is used for selecting “manual mode”. When the
controller is running in MANUAL mode, the LED above the push button
illuminated. The Start and Stop push buttons control the starting and
stopping of the Genset..
START / VALUE INCREASE “+” Push Button
The push button is used for manually start the Genset .When the
controller is in MANUAL mode, press this push button to start the
generator.
When in parameter setting mode, this push button is used to increase
values.
STOP / RESET / VALUE DECREASE “-” Push Button
The push button is used for MANUALLY stops the Genset. When the
controller is in MAN mode, press and hold this button more than 2sec
to stop the Genset.
If failure occurs, press this button, the shutdown alarm lockout can be
cleared.
When in parameter setting mode, this push button is used to decrease
values.
COMMEN FAILURE LED
LED will flash when pre-alarm (Warning) occurs.
LED will illuminate permanently when shutdown alarm occurs.