DCP-10
Page 24/27
9.2 Setting running parameters
For example: (setting CT ratio at 1000/5, then CT should be configured as 200)
Operation
Description
Press and hold “
” 2sec, enter into parameters setting menu, then LCD
displays:
press “
”, then LCD displays:
Press “
”, prompted enter password, then LCD displays:
Press “
” or “
” prompted enter password: (2213), then press “
”
again, press “
” or “
” to change parameter, change at 200, then LCD
displays:
Press “
” to confirm
,
then press “
”, then LCD displays:
Press “
” again to quit, or press and hold “
” more than 2s also can
quit, then LCD displays:
For example: (setting controller crank attempt at 2)
Operation
Description
Press and hold “
” 2sec, enter into parameters settings menu, then
LCD displays:
Press “
” 28 times and then press “
”, then LCD displays:
press “
” prompted enter password, then LCD displays:
Key in password: (2213), press “
”, then LCD displays:
Press “
” or
“
” change parameter, change at 2, Press “
” to confirm
change, and then press and hold “
” for more than 2sec will quit
parameter settings menu.