
DCP-10
Page 16/27
Code Table for Failure:
Name
Code
Name
Code
CHARGE FAILURE
ENGINE HIGH TEMP
BATT. UNDER VOLT
OVER SPEED
BATT. OVER VOLT
UNDER SPEED
START FAILURE
OVER CURRENT
STOP FAILURE
GEN. OVER VOLT
EMERGENCY STOP
GEN. UNDER VOLT
LOW OIL PRESS
P-SENSOR OPEN
NOTE:
Engine speed signal is derived from the frequency of generator output
voltage, it is used for control and failure protection parameters, for the
convenience of user, some data is expressed by RPM, RPM = Hz * 60 /
pair of poles.
While the Genset is running, if there are high coolant temperature, low oil
pressure or over speed failure occurs, the controller will shutdown it
immediately without delay. During the cool down period, if there is low oil
pressure failure, the alarm will be active no matter if there is idle function.
CAUTION:
During the period of safety-on delay, low oil pressure protection is
inactive. To avoid starting an engine with no oil, you must make sure the
oil levels are normal and the safety-on delay shall be carefully and
properly set for the first commissioning.
Содержание DCP-10
Страница 1: ...Manual DCP 10 Genset Controller...
Страница 32: ......