Talentum UV/IR Test Unit Procedure
0044-112-01
How to modify the Test Unit
1)
Remove the four screws that hold on the plate and filter that cover the bulb of the Test Unit
using a 2.5mm allen/hex key;
2)
Remove the black cover and the blue filter behind it from the front of the torch including the
four screws and washers and put them aside.
3)
Fit the modification assembly so that the seven optical filters are positioned over the test
torch bulb and the UV source sits above the test torch on the keypad side as shown below
4) Take the new filter arrangement and, without removing any parts, use the four new screws to
locate it on the front of the Test Unit. Gently tighten the four screws so that the filter is held
securely.