Talentum UV/IR Test Unit Procedure 

 

 

 

0044-112-01 

 

To activate the main output source, press and hold down the * button on the Test Unit. It does not need 
to be  waved  back  and  forth  as  it  already  mimics  the characteristic  flicker  of  a  real  flame. The  flame 
detector is expected to alarm within 30 seconds. 

 

 

 

 

 

 

 

 

 

 

 

If a device is found to be insensitive to this flame sensor test, please contact your FFE account manager 
for support. 

Summary 

Test description 

Flame dimensions 

Distance to detector 

Test Unit with UV/IR Adapter 

(N/A) 

50-70cm (1-2¼ ft) 

 

Warranty 

Warranty  is  not  affected  by  using  these  components  with  the  test  unit,  provided  that  no  other 
modifications are implemented. The test unit should still be serviced and maintained in accordance with 
the instructions. 

The  new  free-issue  components  carry  a  limited  1-year  warranty  against  defects  in  manufacture,  in 
isolation from the rest of the Test Unit.  Any damage resulting from wear and tear or improper use is 
not covered by this warranty. 

Part number: 1800-009 

 

Содержание Talentum UV/IR Test Unit

Страница 1: ...t so that it is optimised for testing UV IR flame detectors Modifying the Test Unit with the adapter changes the output IR and UV spectrum so it closely matches a yellow flame This subjects the Talentum detector to a test more suited to identifying a performance issue The output of the torch without this modification matches a blue flame Health and Safety In accordance with the Talentum User Guide...

Страница 2: ...he front of the torch including the four screws and washers and put them aside 3 Fit the modification assembly so that the seven optical filters are positioned over the test torch bulb and the UV source sits above the test torch on the keypad side as shown below 4 Take the new filter arrangement and without removing any parts use the four new screws to locate it on the front of the Test Unit Gentl...

Страница 3: ...orming the test and that its bulb is working correctly If the Test Unit is insufficiently charged or the bulb has failed it is likely to result in test failure no response from the detector If testing a UV version of Talentum turn on the UV lamp using the switch at the back of the UV lamp unit A green LED will indicate that the UV lamp unit is on Hold the Test Unit as still as possible at a distan...

Страница 4: ...nager for support Summary Test description Flame dimensions Distance to detector Test Unit with UV IR Adapter N A 50 70cm 1 2 ft Warranty Warranty is not affected by using these components with the test unit provided that no other modifications are implemented The test unit should still be serviced and maintained in accordance with the instructions The new free issue components carry a limited 1 y...

Отзывы: