Angle seat valve with diaphragm actuator VZXA-...-M

English

. . . . . . . . . . . . . . . .

1

About this document

This document describes the use of the above-mentioned product. It contains
additional information for the implementation of the product in safety-oriented
systems (safety handbook in accordance with IEC 61508).

For all available product documentation 

è

 www.festo.com/pk

1.1 Specified standards

Version status

IEC 61508-1:2010 part 1, 2, 4…7

IEC 61511:2016

Fig. 1

2

Safety

2.1 General safety information

 The product may only be used in its original status without unauthorized modi­

fications.

 Use the valve only in the flow direction indicated.
 Only use the product if it is in perfect technical condition.
 Take into consideration the ambient conditions at the location of use.

Media

 Only use media in accordance with specifications 

è

 Technical data.

 Use only media that will not cause dangerous reactions if mixed.
 Do not operate the product with chemically unstable gases, abrasive media

or solid materials.

 If water is used: up to approx. 1000 ppm of chloride content is permitted.

Avoid tensile stresses.

 If aggressive media are used: limit medium temperature to 65 °C.

Actuator

 Do not open the actuator (pressure in the actuator or loaded spring).
 Avoid mechanical stresses on the valve. Do not use the actuator as a lever.

Return to Festo

Hazardous substances can endanger the health and safety of personnel and cause
damage to the environment. To prevent hazards, the product should only be re­
turned upon explicit request by Festo.
 Consult your regional Festo contact.
 Complete the declaration of contamination and attach it to the outside of the

packaging.

 Comply with all legal requirements for handling hazardous substances and

transporting dangerous goods.

2.2 Intended use

The angle seat valve VZXA-...-M is intended to shut-off gaseous or liquid media in
piping systems.
 To control liquid media, use only the product variant VZXA-B... (media flow under

valve seat).

2.3 Training of specialized personnel

Work on the product should only be conducted by qualified personnel. The quali­
fied personnel must be familiar with installation of process automation systems.

3

Further information

– Accessories 

è

 www.festo.com/catalogue

– Spare parts 

è

 www.festo.com/spareparts

4

Service

 Contact the regional Festo contact if you have technical questions

è

 www.festo.com.

5

Information on functional safety

5.1 Attainable safety rating

The product is suitable for use as an element in a safety-related system in accord­
ance with IEC 61511.
– In low-demand mode up to SIL 2
– In high-demand mode up to SIL 2.
Taking into account the necessary minimum hardware fault tolerance from HFT = 1,
the product can also be used up to SIL 3 with a redundant design of the entire system.

Note

The suitability for certain applications can only be determined in connection with
the evaluation of further components of the subsystem.

5.2 Safety function

Single-acting valves

The safety function consists of taking the initial position on request. The request is
made by removing the operating pressure.
– Valves with control function NO: The valve opens completely and remains open

until operating pressure is applied.

– Valves with control function NC: The valve closes completely and remains closed

until operating pressure is applied.

Double-acting valves

The safety function consists of taking the desired position on request. Supply of
external energy is required for this.

5.3 Operating conditions

– General notes on safe operation 

è

 Chapter 2.

– Periodic tests (performance test) 

è

 Chapter 12.

– Ambient conditions and additional technical specifications 

è

 Chapter 16.

5.4 Limitations of application

The service life is not limited if the operating conditions are complied with.
– Maximum admissible interval for a complete performance test: seven years.

5.5 Characteristic values

Safety standards (in accordance with IEC 61508)

Value

Route of assessment

2

H

 / 1

S

Type of Sub System

Type A

Mode of Operation

Low Demand and
High Demand

Assumed Test Interval

T

i

1 a

Confidence Level

1-

á

95 %

Hardware Fault Tolerance

HFT

0

Lambda Dangerous 

ë

D

1,36 · 10

-7 

/ h

Lambda Dangerous Undetected

ë

DU

1,36 · 10

-7 

/h

Mean Time To Dangerous Failure

MTTF

D

7,37 . 10

6

 h

Proof Test Coverage

PTC

95 %

Low Demand Mode

Assumed Demands per Year

n

op

1 / a

Average Probability of Failure on Demand

PFD

avg

5,95 · 10

-4

High Demand Mode

Assumed Demands per Year

n

op

1 / h
(8760 / a)

Probability of dangerous Failure per Hour

PFH

1,36 · 10

-7

 / h

Fig. 2