background image

Solenoid valve
VZWP-L-M22C-...-P4-...

Festo AG & Co. KG

Postfach
D-73726 Esslingen
++49/711/347-0
www.festo.com

(en) Operating instructions

749 647
1007NH

Original: de

1

Design

3

7

aJ

1

aA

6

2

5

4

8

9

1

Port 1: Input

2

Valve body

3

Electrical plug connector with seal
and mounting screw

4

Knurled nut

5

O-ring

6

Solenoid coil

7

O-ring

8

Armature guiding tube

9

Port 2: Output

aJ

Arrow for flow direction

aA

Thread for mounting bracket

Fig. 1

2

Function

The solenoid valve VZWP–L–M22C–... is a servo controlled 2/2-way valve with
solenoid coil.
The solenoid valve VZWP–L–M22C–... is closed when de-energised (Normally
Closed - NC). When power is supplied, the differential pressure is relieved from the
secondary side of the piston via the servo hole. The effective differential pressure
lifts the piston away from the valve seat.
The pilot function of the valve actuator can be used to control high pressures with
large nominal diameters by means of small solenoid coils.
The minimum differential pressure must always be present to ensure smooth func-
tioning of the servo control (

Î

Technical data).

3

Application

Solenoid valves of the series VZWP–L–M22C–... are intended to control the flow of
gaseous and fluid media in rigid piping systems.
• The product may only be used in its original state without unauthorised modific-

ations. Only the mounting and commissioning activities described in these oper-
ating instructions are permissible. Do not open the valve body or dismantle the
armature guiding tube.

• Do not use the product in closed circuits.
• Do not use the VZWP solenoid valve as a safety component.
• Observe the permissible limit values and specifications (

Î

Technical data).

• Use the product only in perfect technical condition.
• Use only neutral operating media as per specification. Before using other oper-

ating media, please contact our customer support.

• Operation with chemically unstable gases, abrasive media and solids is imper-

missible.

• Use the solenoid valve only in the marked flow direction.
• Comply with all applicable national and international regulations.

4

Product variants

Features

Type code

Description

Type

VZWP

Servo controlled, solenoid actuated process valve

Valve type

L

In-line valve

Valve function

M22C

2/2-way valve, normally closed (NC), mechanical
reset

Connection to valves
and fittings

G14 to G1

Pipe thread per DIN ISO 228

N14 to N1

NPT pipe thread per ANSI B 1.20.1

Nominal size (DN)

130
250

13 mm
25 mm

Sealing material


V

NBR
FKM

Nominal voltage

1
2A
3A

24 V DC
110 V AC (50-60 Hz)
230 V AC (50-60 Hz)

Electrical connection

P4

Plug socket, 3-pin

Operating pressure

40

Max. 40 bar

Fig. 2

5

Transport and storage

• Ensure the following storage conditions: short storage periods in cool, dry,

shaded and corrosion resistant locations.

6

Installation

Note

• Installation only by qualified personnel.
• Electrical connection only by qualified electricians.
• Avoid contamination. In this way you will prevent small holes from becoming

blocked (e.g. servo hole) and restriction or blockage of the function.

• Avoid mechanical stresses especially on the solenoid coil and the armature

guiding tube.

• Ensure sufficient thermal circulation at the installation location.

1. Before installation, check the system requirements:

– The tubing system is unpressurised and does not hold any medium.
– The pipelines are clean.
– The ends of the pipelines are mounted.
– The power supply is switched off.

2. Put the solenoid valve in its mounting position. Please note the flow direction.

The permissible flow direction is marked by an arrow on the valve body.

3. Screw the ends of the pipelines to the valve ports. Observe the permissible

tightening torques.

4. Establish the electrical connection. Use only the specified plug type (

Î

Tech-

nical data).
– Connect the electrical cable to the plug connector.
– Attach the seal to the electrical contacts.
– Plug in the plug connector and secure it in place with the mounting screw

(torque 0.3...0.5 Nm).

5. Connect the power supply.

Содержание VZWP-L-M22C-P4 Series

Страница 1: ... und mit festen Stoffen ist unzulässig Verwenden Sie das Magnetventil nur in der gekennzeichneten Durchflussrich tung Halten Sie alle geltenden nationalen und internationalen Vorschriften ein 4 Produktvarianten Merkmale Typen schlüssel Beschreibung Typ VZWP Elektrisch betätigtes Prozessventil servogesteuert Ventilart L Muffenventil Ventilfunktion M22C 2 2 Wegeventil in Ruhestellung geschlossen NC ...

Страница 2: ...ca 1 1 5 Nm 11 Wartung und Pflege Prüfen Sie das Magnetventil mindestens alle 6 Monate auf Leckage Prüfen Sie das Magnetventil mindestens alle 6 Monate auf Funktion Reinigen Sie das Ventil regelmäßig außen mit einem weichen Lappen Zulässiges Reinigungsmittel ist Seifenlauge 12 Störungsbeseitigung Störung Mögliche Ursache Abhilfe Magnetventil schließt nicht Magnetventil defekt Magnetventil austausc...

Страница 3: ...ally unstable gases abrasive media and solids is imper missible Use the solenoid valve only in the marked flow direction Comply with all applicable national and international regulations 4 Product variants Features Type code Description Type VZWP Servo controlled solenoid actuated process valve Valve type L In line valve Valve function M22C 2 2 way valve normally closed NC mechanical reset Connect...

Страница 4: ...or leakage at least every 6 months Check the functioning of the solenoid valve at least every 6 months Regularly clean the outside of the valve with a soft cloth The permissible cleaning agent is soap suds 12 Eliminating malfunctions Malfunction Possible cause Remedy Solenoid valve not closing Solenoid valve is defective Replace the solenoid valve Flow direction is incorrect Install the solenoid v...

Отзывы: