3. Depressurise the valve.
4. Allow the device to cool down.
10.1
Cleaning
Regularly clean the outside of the product with a soft cloth. The approved clean-
ing agent is water or detergent (max. 50 °C).
11
Malfunctions
11.1
Fault clearance
Malfunction
Display
Possible cause
Remedy
Status LED is not
on
No supply voltage
Check supply voltage
VPPL does not react.
-
Device faulty
Replace device
Valve exhausts to 0 bar.
-
Supply cable broken
Replace cable
Hardware error, electron-
ics
Replace device
Output stage is switched
off, error bit is set, valve
exhausted to 0 bar
Status LED steady
red
VPPL cable break with
setpoint value signal for
current
Replace cable
Power supply under-
voltage
<
17 V
Increase power supply to
>
20 V
Output stage is switched
off, error bit is set, valve
exhausted to 0 bar
Status LED flash-
ing red
Supply pressure not
present.
See section
è
Tab. 6
12
Disassembly
WARNING!
Risk of injury from compressed air/pressure surge.
Products under pressure can cause personal injury.
•
Before carrying out any work on the product, switch off the compressed air
supply and secure it against being switched back on.
1. Switch off pressure to the pneumatic system.
2. Switch off analogue setpoint signal.
3. Switch off supply voltage and lock switch to prevent reactivation.
4. Allow the device to cool down.
5. Disconnect VPPL electrical connections.
6. Decommission the PREL.
7. Disconnect VPPL mechanical mounting.
13
Disposal
ENVIRONMENT!
Dispose of the product and packaging according to the applicable provisions of
environmentally sound recycling.
14
Technical data
14.1
Technical data, general
VPPL-
…
-0L20H
VPPL-
…
-0L40H
Design
Proportional-pressure regulator
Mounting position
As desired, preferably with display compon-
ents facing upwards (solenoid coil should not
be upside down)
Type of mounting
Flange and thread
Operating medium
Filtered, unlubricated compressed air, grade of
filtration min. 40 µm
Max. permissible input pressure
[MPa]
4
5
[psi]
580
725
[bar]
40
50
Control range
[MPa]
0.02 … 2
0.04 … 4
[psi]
2.9 … 290
5.8 … 580
[bar]
0.2 … 20
0.4 … 40
Control precision, standard 2%
[MPa]
0.04
0.08
[psi]
5.8
11.6
[bar]
0.4
0.8
Max. total leakage when new
[l/h]
<
20
Nominal width
Pressurisation
[mm]
2.5
Exhaust
[mm]
2.5
Temperature of medium
[°C]
+5 … +50
Ambient temperature
[°C]
+5 … +50
Degree of protection in assembled status
IP65 in accordance with EN 60529/A1:2000-02
Operating voltage DC
[V]
21.6 … 27.6
Residual ripple
[%]
max. 10
Max. power consumption
[W]
24
Signal setpoint value DC (analogue input)
Voltage
[V]
0 … 10
VPPL-
…
-0L20H
VPPL-
…
-0L40H
Current
[mA]
4 … 20
Input resistance setpoint value
-V1
[kΩ]
³
100
-A4
[Ω]
£
100
Signal actual value DC (analogue output)
Voltage
[V]
0 … 10
Current
[mA]
4 … 20
Load resistance (analogue output)
-V1
[kΩ]
³
1
-A4
[Ω]
£
600
Materials
Housing
Wrought aluminium alloy
Internal parts
Stainless steel, brass, aluminium
Cover
PAXMD6-GF50gr-P; PA6-GB20, GF10/gr-P
Seals
HNBR
Lubrication
Not PWIS-free
Tab. 7
14.2
Technical data for UL/CSA certification
Electrical data and ambient conditions UL/CSA
Input current
[A]
max. 0.44
Operating pressure
[bar]
max. 0.8
Pollution degree
3
Humidity range
[%]
0 … 90
Installation site
for indoor use only
Max. installation height
[m]
2000
Degree of protection
The degree of protection IP65 is not UL-tested.
Tab. 8 Electrical data and ambient conditions UL/CSA