3. Depressurise the valve.
4. Allow the device to cool down.

10.1

Cleaning

Regularly clean the outside of the product with a soft cloth. The approved clean-
ing agent is water or detergent (max. 50 °C).

11

Malfunctions

11.1

Fault clearance

Malfunction

Display

Possible cause

Remedy

Status LED is not
on

No supply voltage

Check supply voltage

VPPL does not react.

-

Device faulty

Replace device

Valve exhausts to 0 bar.

-

Supply cable broken

Replace cable

Hardware error, electron-
ics

Replace device

Output stage is switched
off, error bit is set, valve
exhausted to 0 bar

Status LED steady
red

VPPL cable break with
setpoint value signal for
current

Replace cable

Power supply under-
voltage

<

 17 V

Increase power supply to

>

 20 V

Output stage is switched
off, error bit is set, valve
exhausted to 0 bar

Status LED flash-
ing red

Supply pressure not
present.

See section

è

 8.2 Re-commissioning

Tab. 6

12

Disassembly

WARNING!

Risk of injury from compressed air/pressure surge.
Products under pressure can cause personal injury.

Before carrying out any work on the product, switch off the compressed air
supply and secure it against being switched back on.

1. Switch off pressure to the pneumatic system.
2. Switch off analogue setpoint signal.
3. Switch off supply voltage and lock switch to prevent reactivation.
4. Allow the device to cool down.
5. Disconnect VPPL electrical connections.
6. Decommission the PREL.
7. Disconnect VPPL mechanical mounting.

13

Disposal

ENVIRONMENT!

Dispose of the product and packaging according to the applicable provisions of
environmentally sound recycling.

14

Technical data

14.1

Technical data, general

VPPL-

-0L20H

VPPL-

-0L40H

Design

Proportional-pressure regulator

Mounting position

As desired, preferably with display compon-
ents facing upwards (solenoid coil should not
be upside down)

Type of mounting

Flange and thread

Operating medium

Filtered, unlubricated compressed air, grade of
filtration min. 40 µm

Max. permissible input pressure

[MPa]

4

5

[psi]

580

725

[bar]

40

50

Control range

[MPa]

0.02 … 2

0.04 … 4

[psi]

2.9 … 290

5.8 … 580

[bar]

0.2 … 20

0.4 … 40

Control precision, standard 2%

[MPa]

0.04

0.08

[psi]

5.8

11.6

[bar]

0.4

0.8

Max. total leakage when new

[l/h]

<

 20

Nominal width

Pressurisation

[mm]

2.5

Exhaust

[mm]

2.5

Temperature of medium

[°C]

+5 … +50

Ambient temperature

[°C]

+5 … +50

Degree of protection in assembled status

IP65 in accordance with EN 60529/A1:2000-02

Operating voltage DC

[V]

21.6 … 27.6

Residual ripple

[%]

max. 10

Max. power consumption

[W]

24

Signal setpoint value DC (analogue input)

Voltage

[V]

0 … 10

VPPL-

-0L20H

VPPL-

-0L40H

Current

[mA]

4 … 20

Input resistance setpoint value

-V1

[kΩ]

³

 100

-A4

[Ω]

£

 100

Signal actual value DC (analogue output)

Voltage

[V]

0 … 10

Current

[mA]

4 … 20

Load resistance (analogue output)

-V1

[kΩ]

³

 1

-A4

[Ω]

£

 600

Materials

Housing

Wrought aluminium alloy

Internal parts

Stainless steel, brass, aluminium

Cover

PAXMD6-GF50gr-P; PA6-GB20, GF10/gr-P

Seals

HNBR

Lubrication

Not PWIS-free

Tab. 7 

14.2

Technical data for UL/CSA certification

Electrical data and ambient conditions UL/CSA

Input current

[A]

max. 0.44

Operating pressure

[bar]

max. 0.8

Pollution degree

3

Humidity range

[%]

0 … 90

Installation site

for indoor use only

Max. installation height

[m]

2000

Degree of protection

The degree of protection IP65 is not UL-tested.

Tab. 8 Electrical data and ambient conditions UL/CSA