Tab. 15: Circuit diagrams for sensor module
7
Commissioning
7.1
Commissioning the sensor
•
Switch on operating voltage.
Ä
RUN mode is active.
To activate the RUN mode at any time, press and hold the Edit button for 3
seconds.
7.2
Setting switching point A
Switching output OutA is preset for distance monitoring. The switching point for
OutA must be set or taught manually.
Option 1: manually setting the switching point for OutA
1. Press the Edit button.
Ä
EDIT mode is active. [OutA] flashes. Lock flashes with active security
blocking.
2. Enter the set security code using the A or B pushbutton.
3. Press the Edit button to confirm the selection.
Ä
[SP] flashes.
4. Set switching point with the A or B pushbutton.
5. Press and hold the EDIT button for 3 seconds.
Ä
RUN mode is active.
Option 2: teaching-in the switching point for OutA
1. Establish the desired switching distance between the object and the meas-
uring nozzle.
2. Press and hold the A pushbutton.
3. Also press the Edit button.
–
[OutA] and [TeachIn] flash. The value is adopted as the switching
point.
–
[Lock] flashes: security lock active. The value is buffered.
4. Enter the set security code using the A or B pushbutton.
5. Press the Edit button.
–
[OutA] and [TeachIn] flash. The cached value is accepted as the
switching point.
–
RUN mode is active.
7.3
Menu structure (EDIT mode)
Some menu options or setting values are not applicable depending on the product
variant and the selected switching function.
Fig. 13: EDIT mode menu structure
Key
Meaning
Edit button
A or B pushbutton
bold
Factory setting
1)
Menu column only for PNLK-VB/A
2)
Menu item only with PNLK-VB
3)
Menu item only for PNLK-VB/A
4)
Menu column and menu item only for 2P/2N
Tab. 16: Legend for menu structure EDIT mode