SFAM
14
Festo – SFAM – 2017-09c English
Note
The compressed air must not contain ester oils.
Note
The SFAM must not be installed directly behind a pressure regulator or filter regulator to
comply with the specified accuracies.
After the filter regulator MS…-LFR or pressure regulator MS…‐LR , build a branching
module upstream of SFAM.
–
Grid dimension 62: MS…-FRM-
½
–
Grid dimension 90: MS…-FRM-
¾
3. Place the module connectors type MS…-MV in the slots of the individual devices. Accordingly, a seal
is required between the individual devices.
4. Fasten the module connectors type MS…-MV with 2 screws.
4.2
Electrical connection
Warning
Only use power sources which guarantee reliable electrical isolation of the operating
voltage according to IEC/DIN EN 60204-1. Also observe the general requirements for
PELV power circuits according to IEC/DIN EN 60204-1.
Switched-mode power supplies are permitted, provided that they ensure reliable
separation in accordance with EN 60950/VDE 0805.
Note
Long signal lines pick up more interference.
Make sure that the signal lines are always shorter than 30 m.
Note
The binary outputs at pin 2 and pin 4 can be wired as PNP or NPN connections as
needed.
Make sure that you also configure the binary outputs according to your wiring
è
Chapter 5.5.3.