background image

5.4 Connecting components

Port [X0], [X1], …

Signal

0

1

+24 V DC output

2

Output –

3

0 V DC output

Fig. 6

Port [X4]

1)

Signal

0

Functional earth FE

1

2

3

1)

The ports X4.0 … X4.3 are interconnected in the terminal strip.

Fig. 7

Port [XD]

1)

Signal

0

+24 V DC load voltage supply U

OUT

1

2

0 V DC load voltage supply U

OUT

3

1)

The connections XD.0 and XD.1 and also XD.2 and XD.3 are interconnected in the terminal strip.

Fig. 8

6

Conveying and storage

 Observe specifications for the environmental and storage conditions

è

 13 Technical data.

7

Connection

 Mount the module as outlined in the “Instructions for using system CPX-E”

è

 1.1 Further applicable documents.

8

Installation

Note

Malfunction due to electromagnetic interference.
 Only connect shields at the port for functional earth (FE) 

è

 Fig. 4.

1. Make sure that the power supply is switched off.
2. Connect the lines to the terminal strips as outlined in the “Instructions for using

system CPX-E” 

è

 1.1 Further applicable documents.

9

Commissioning

You can find information on commissioning system CPX-E in the “Instruc­

tions for using system CPX-E”. Information on the parameters can be found

in the “Description of system CPX-E” and the descriptions of the modules

being used 

è

 1.1 Further applicable documents.

Behaviour of the display components after error-free commissioning

[

P

] (red)

1)

[X0], [X1], … (red)

[PL] (green)

Off

Off

Lights up

1)

Flashes once briefly at the initialisation of the CPX-E system

Fig. 9

Information on troubleshooting in the event of incorrect behaviour can be
found in the “Description of system CPX-E” and the descriptions of the
modules being used 

è

 1.1 Further applicable documents.

10

Diagnostics and fault clearance

10.1 Diagnostics options

Various options are available for diagnosing errors:
– Internal system diagnostics
– LED indicators on the product

10.2 Internal system diagnosis

The internal system diagnostics process is described in the “Description of
system CPX-E” and the module descriptions

è

 1.1 Further applicable documents.

10.3 LED indicators

Module error [

P

]

1)

LED (red)

Significance

Remedy

Lights up

Short circuit/overload on actuator
supply

 

or module defective

1. Check the connected actuators,

eliminate short circuit/overload.

2. Switch the power supply U

EL/SEN

off and on again.

2)

Channel error.

è

 Fig. 11

Load voltage supply U

OUT

 not present

or undervoltage

3)

 Check load voltage supply U

OUT

.

Off

normal operating status

1)

Flashes once briefly at the initialisation of the CPX-E system

2)

The necessity of performing this step depends on the configuration of the parameter “Behaviour after
SCS” 

è

 Description analogue output modules CPX-E-…AO-U-I.

3)

If the “Load voltage supply undervoltage diagnostics” parameter is activated 

è

 Description of ana­

logue output modules CPX-E-…AO-U-I.

Fig. 10

Channel error [X0], [X1], …

LED (red)

Significance

Remedy

Lights up

Wire break/idling current output

1)

 Check lines and actuators and

replace where required.

Value exceeding nominal range/value
falling below nominal range

 Check analogue input.
 Check the parameterised limit

values.

 If necessary, deactivate monitoring.

Parameterisation errors

 Check parameterisation and adjust.

Short circuit/overload or
undervoltage actuator supply

è

 Fig. 10

Off

No channel error

1)

If output value 

,

 2 mA: 

– Error definitely incoming if R

L

 

š

 5 Ω

– Error definitely outgoing if R

L

 

 10 Ω

Fig. 11

Load voltage supply U

OUT

 [PL]

LED (green)

Significance

Remedy

Lights up

Load voltage supply U

OUT

 present

Off

Load voltage supply U

OUT

 not present

or undervoltage

 Check load voltage supply U

OUT

.

Fig. 12

11

Service

Note

Accumulation of heat due to reduced air supply to electronics.
 Keep the ventilation slots free and regularly remove contamination.

12

Disposal

 Dispose of the packaging and the product at the end of its useful life through

environmentally friendly recycling in accordance with applicable specifications.

13

Technical data

General remarks

Key feature

Specification/value

General technical data, system CPX-E

Description of system CPX-E 

è

 1.1 Further applicable documents

Dimensions (length x width x height)

[mm]

124.3 x 18.9 x 76.6

Product weight

1)

[g]

96

Mounting position

Vertical/horizontal

Ambient temperature

[°C]

–5 … +60 (–5 … +50)

2)

Storage temperature

[°C]

–20 … +70

Air humidity (non-condensing)

[%]

0 … 95

Assigned address space (inputs/outputs)

[Bit]

–/64

Module code/submodule code (CPX-E-specific)

142/2

Module identification

E-4AO

Degree of protection in accordance with EN60529

IP20

Protection against electric shock (protection
against direct and indirect contact in accordance
with IEC 60204-1)

Through the use of PELV circuits
(Protected Extra-Low Voltage)

Electromagnetic compatibility

To EN 61000-6-2/-4

1)

Including linking

2)

With horizontal mounting position

Fig. 13

Отзывы: