Motor phases U, V, W
–
PE connection
[X6A]
Pin
Function
Description
4
PE
Protective earth motor
3
W
Third motor phase
2
V
Second motor phase
1
U
First motor phase
Tab. 56 Motor phase connection
The cable shield of the motor cable is placed on the support surface on the lower part of the housing
and fastened with the shield clamp.
Requirements for the counterplug
Design
FKIC 2.5 HC/4-ST-5.08 from
Phoenix Contact or compatible
Power contacts
4
Nominal current
16 A
Rated voltage (III/2)
320 V
Grid dimension
5.08 mm
Strip length
10 mm
Tab. 57 Requirements for the counterplug
Requirements for the connecting cable
Wires and shielding
At least 8 wires
–
4 power wires shielded
–
2 x holding brake, separately shielded
–
2 x motor temperature, separately shielded
Design
Use only cables for which safe separation is
ensured between the motor phases and the
shielded signals of the holding brake and motor
temperature sensor.
è
8.9.3 Shield support of the motor cable
Max. cable length
è
Technical data for the integrated mains filter
Max. capacity
<
250 pF/m
Installation