CMGA-E1 specific error codes that are not listed in the CMGA installation instructions

Alarm code

A 2101 / A 2101

Description

Error in transmission telegram, basic unit

Cause

Basic unit does not receive an answer from CMGA-E1

Remedy

Check installation between basic unit and CMGA-E1

Alarm code

A 2105 / A 2106

Description

CRC error, receipt telegram from the basic module

Cause

Sent CAN data framework from the basic unit is damaged - incorrect serial

number CMGA-E1 is configured

Remedy

Configure the CMGA-E1 with the correct serial number

Alarm code

A 2107 / A 2108

Description

CRC error, receipt telegram from basic unit

Cause

Sent CAN data framework from the CMGA-E1 is damaged

Remedy

Check the installation between basic unit and CMGA-E1

Alarm code

A 2109 / A 2110

Description

CRC error, transmission telegram from the basic module

Cause

Received CAN data framework from the CMGA-E1 is damaged

Remedy

Check the installation between basic unit and CMGA-E1

Fatal error code

F 3821

Description

Status of the output EAA1.1 is incorrect

Remedy

Check the output circuit (short circuit)

Check the configuration (input or output)

Fatal error code

F 3823

Description

Status of the output EAA1.2 is incorrect

Remedy

Check the output circuit (short circuit)

Check the configuration (input or output)

Fatal error code

F 3825

Description

Status of the output EAA1.3 is incorrect

Remedy

Check the output circuit (short circuit)

Check the configuration (input or output)

Fatal error code

F 3827

Description

Status of the output EAA1.4 is incorrect

Remedy

Check the output circuit (short circuit)

Check the configuration (input or output)

Содержание CMGA-E1

Страница 1: ...Description Installation manual Extension module inputs outputs 8037553 1404a Extension module CMGA E1...

Страница 2: ...es Caution Dangers that can result in light injuries or serious material damage Other symbols Note Material damage or loss of function Recommendation tip reference to other documentation Necessary or...

Страница 3: ...2 1 Operation and service 4 3 Modification of an installation 5 4 Commissioning 6 5 Configuration 8 6 LEDs CMGA E1 10 7 Switch on sequences basic module CMGA 10 8 Error types of the CMGA 11 9 Change h...

Страница 4: ...used in each case e g CMGA B1 M0 L0 A0 The subsequently used term safe refers in each case to the classification as safe function for the application up to PL e in accordance with EN ISO 13849 1 or S...

Страница 5: ...gnals 1 2 3 Fig 1 Front CMGA E1 3 Modification of an installation Commissioning or modification of an installation of the CMGA can only be performed by qualified per sonnel Contact the company that pr...

Страница 6: ...B1 M2 L2 A0 2 CMGA E1 3 CMGA E1 CO 1 2 3 Fig 2 Example CMGA B1 M2 L2 A0 CMGA E1 CMGA E1 CO Basic module extension module I O extension module CANopen Power supply to the CMGA E1 takes place via X11 pl...

Страница 7: ...1 6 EAA1 6 X22 1 IO07 I O extension 7 EAE1 7 EAA1 7 X22 2 IO08 I O extension 8 EAE1 8 EAA1 8 X22 3 IO09 I O extension 9 EAE1 9 EAA1 9 X22 4 IO10 I O extension 10 EAE1 10 EAA1 10 X13 1 X13 2 X13 3 DO0...

Страница 8: ...ig 4 CMGA device selection Double click in the main menu on the entire device to open the configuration dialog Fig 5 CMGA E1 In this window write the serial number of the CMGA E1 see rating plate into...

Страница 9: ...CMGA E1 Festo GDCP CMGA E1 EN 1404a 9 Fig 6 Device configuration 1 2 1 Configure IO01 as input 2 Configure IO02 as output Fig 7 Example...

Страница 10: ...cription 1 STARTUP Synchronisation checking of the configuration firmware data 2 SENDCONFIG Synchronisation checking of the configuration firmware data area checking 3 STARTUP BUS Initialization of th...

Страница 11: ...be reset by switching the CMGA POR off and on Alarm Functional error caused by an external process Both systems continue to run cyclically and serve all re quests from the communication interfaces Sen...

Страница 12: ...heck the installation between basic unit and CMGA E1 Alarm code A 2109 A 2110 Description CRC error transmission telegram from the basic module Cause Received CAN data framework from the CMGA E1 is da...

Страница 13: ...833 Description Status of the output EAA1 7 is incorrect Remedy Check the output circuit short circuit Check the configuration input or output Fatal error code F 3835 Description Status of the output...

Страница 14: ...the safety test report 10 Maintenance 10 1 Replacement of a CMGA module After replacement of a CMGA module it must be ensured that the replacement module includes the same configuration The test repor...

Страница 15: ...l I 24 VDC 20 mA Type1 as per EN 61131 2 Ratings safe digital O EAA1 1 to EAA1 10 24 VDC 250 mA Ratings not safe digital O O1 1 and O1 2 24 VDC 100 mA Pulse outputs Max 250 mA Environmental data Tempe...

Страница 16: ...xpress authorization is prohibited Offenders will be liable for damages All rights reserved in the event that a patent utility model or design patent is registered Copyright Festo AG Co KG Postfach D...

Отзывы: