![background image](http://html.mh-extra.com/html/festo/cesa-gw-as-pb/cesa-gw-as-pb_installation-and-operation-owners-manual_2283507037.webp)
CESA-GW-AS-PB Description
36
6.8.3
OPERATION MODE
Main menu || SETUP || OPERATION MODE ||
This function shows the current operation mode of the AS-i master:
The operation mode can be changed with “Change”.
Parameters and configuration data can be modified in configuration mode, only.
6.8.4
STORE ACTUAL (store currently detected configuration)
Main menu || SETUP || STORE ACTUAL||
This function can only be executed in configuration mode.
This function enables currently detected slaves on the selected AS-i network to
be stored in the configuration of the AS-i Master.
If "Store" was successful, the LED "Config error" is turned off. The configuration is
stored and the configuration error has been eliminated.
However, if one of the connected slaves exhibits a peripheral fault, the LED "Con-
fig error" will flash.
If the AS-i master is in protected mode, the error message "Failed No Config
Mode" will appear:
Address 0 is not a permitted operation address for a slave. If an AS-i slave with
this address exists, storing the configuration will still be confirmed with "OK".
However, the configuration error remains.
OPERATION MODE
CONFIG MODE
CHANGE
PROTECTED MODE: protected operating mode
CONFIG MODE: configuration mode
STORE ACTUAL
CONFIGURATION
STORE
Содержание CESA-GW-AS-PB
Страница 1: ...Description AS i Gateway English Gateway AS i PROFIBUS CESA GW AS PB 749962 1002NH ...
Страница 2: ......
Страница 4: ......