CESA-GW-AS-PB Description
72
93
Error while changing slave address: New address could only be stored volatile
in the slave.
94
Error while changing the slave address in protected operating mode: Slave has
wrong configuration data.
95
The error 95 is caused by a superfluous slave and not by a missing slave. That
is why the slave address is occupied by this superfluous slave.
(In the protected mode the slave addresses which caused any configuration
error can be displayed by pressing the SET button. AS-i master without graph-
ical display are not able to differentiate between a missing slave, an incorrect
slave or a redundant slave. All incorrect addresses are displayed.
By pressing the SET button 5 sec. the displayed address starts to flash. Press-
ing the SET button again the master attempts to program the slave at the
address 0 to the incorrect address.)
Содержание CESA-GW-AS-PB
Страница 1: ...Description AS i Gateway English Gateway AS i PROFIBUS CESA GW AS PB 749962 1002NH ...
Страница 2: ......
Страница 4: ......