4.2 Commissioning

B

Commissioning must be carried out by Quali-
fied Personnel. Checks to be done at first
lighting, and after all maintenance operations
that involved disconnection from the systems
or work on safety devices or parts of the boil-
er:

Before lighting the boiler:

Open any on-off valves between the boiler and the system.

Check the tightness of the gas system, proceeding with caution and using a soap
and water solution to detect any leaks in connections.

Fill the water system and make sure all air contained in the boiler and the system
has been vented.

Make sure there are no water leaks in the system or boiler.

Check the correct connection of the electrical system.

Make sure the unit is connected to an efficient earthing system.

Make sure the pressure and gas flow values are those required for heating.

Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler

Boiler lighting

Open the gas cock ahead of the boiler.

Vent the air from the pipe ahead of the gas valve.

Turn on or insert any switch or plug ahead of the boiler

Turn the main switch (ref. 2 - fig. 1) to ON.

Light the pilot flame as described in sec. 2.3.

Set the control thermostat (ref. 4 - fig. 1) to a value above 50°C and that of a possible
room thermostat to the desired temperature value. At this point the burner will light
and the boiler will start to work automatically, controlled by its adjustment and safety
devices.

B

If, after correctly carrying out the lighting pro-
cedure, the burners fail to light and the indica-
tor button lights up, wait about 15 seconds
and then press the above-mentioned button.
The reset controller will repeat the ignition cy-
cle. If the burners do not light after the second
attempt, refer to the section *** 'Troubleshoot-
ing' on page 32 ***.

A

In case of a power failure while the boiler is working, the burners will go out and
automatically relight when the power is restored.

Checks during operation

Make sure the fuel circuit and water systems are tight.

Check the efficiency of the flue and fume ducts while the boiler is working.

Make sure the water is circulating properly between the boiler and the system.

Check correct lighting of the boiler, by turning it on and off several times using the
room thermostat or boiler thermostat.

Make sure the fuel consumption indicated on the meter matches that given in the
technical data table in cap. 5.

Turning off

To temporarily turn the boiler off, just the turn main switch (ref. 2 - fig. 1) to 

OFF

.

To turn the boiler off for an extended period:

Turn the main switch (ref. 2 - fig. 1) to 

OFF

;

Press and turn the control knob 1 to position 

“C”

 (fig. 2).

Close the gas cock ahead of the boiler;

Disconnect the power to the unit;

B

To avoid damage caused by freezing during
long shutdowns in winter, it is advisable to
drain all water from the boiler and the system;
or add a suitable antifreeze to the heating sys-
tem.

4.3 Maintenance

B

The following operations must only be carried
out by Qualified Personnel.

Seasonal inspection of the boiler and flue

It is advisable to carry out the following checks on the unit at least once a year:

The control and safety devices (gas valve, thermostats, etc.) must function correctly.

The fume ducts must be free of obstructions and leaks.

The gas and water systems must be tight.

The burner and boiler shell must be clean. Follow the instructions in the next section.

The pilot burner must be properly positioned and free of deposits (see fig. 10).

The water pressure in the system when cold must be about 1 bar; otherwise, bring
it to that value.

The expansion tank, if present, must be filled.

The gas delivery and pressure must match that specified in the technical data table
(see sec. 5.3).

The circulating pumps must not be blocked.

Safety devices

The 

PEGASUS 23 T - 32 T - 35 T - 45 T

 boiler is equipped with devices that guarantee

safety in case of operation faults.

Manual reset temperature limiter (safety thermostat)

This device prevents the water temperature in the system from exceeding boiling point.
The maximum intervention temperature is 110°C and causes boiler shutdown.
Reinstatement can only occur with cooling of the boiler (the temperature must drop by at
least 10°C) and identification and consequent elimination of the problem that caused the
shutdown.

Fume evacuation safety device (fume thermostat)

The boiler has a fume evacuation control device. In case of anomalies in the fume evac-
uation system with consequent return of burnt gases into the room, the unit shuts down.
The anti-wind hood has a fume thermostat for measuring and controlling the fume tem-
perature.
Any leakage of burnt gases into the room causes a temperature increase detected by the
bulb, causing the boiler to shut down within 2 minutes and stopping the gas to the burner.
In case of fume thermostat intervention, manually reset the thermostat (see sec. 2.6).
The boiler will start working again.
If the thermostat has to be replaced due to a fault, only use original accessories and en-
sure that the electrical connections and bulb positioning are correctly carried out.

B

THE FUME THERMOSTAT MUST NOT BE
EXCLUDED FOR ANY REASON!

Opening the front casing

To open the front panel of the boiler, see the sequence in fig. 7.

fig. 7 - Front panel opening

B

Before carrying out any operation inside
the boiler, disconnect the power and close
the gas cock upstream.

1

2

Содержание PEGASUS 23 T

Страница 1: ...LLAZIONE E LA MANUTENZIONE ES INSTRUCCIONES DE USO INSTALACI N Y MANTENIMIENTO TR KULLANMA KURULUM VE BAK M TALIMATLAR EN INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE FR INSTRUCTIONS D UTILISATIO...

Страница 2: ...olgersi al fornitore Lo smaltimento dell apparecchio e dei suoi accessori deve essere effettuato in modo adeguato in conformit alle norme vigenti Le immagini riportate nel presente manuale sono una ra...

Страница 3: ...le normali attivit di manutenzione 3 3 Collegamenti idraulici Avvertenze La potenzialit termica dell apparecchio va stabilita preliminarmente con un calcolo del fabbisogno di calore dell edificio sec...

Страница 4: ...e PEGASUS 23 T 32 T 35 T 45 T vengono prodotte predisposte per il fun zionamento a gas naturale o per gas liquido La prova e la taratura della pressione viene fatta in fabbrica Bisogner per al momento...

Страница 5: ...erruttore generale rif 2 fig 1 sulla posizione OFF Premere e ruotare la manopola di comando 1 in posizione C fig 2 Chiudere il rubinetto del gas a monte della caldaia Togliere corrente all apparecchio...

Страница 6: ...del ter mostato fumi montato nella parte posteriore della camera fumi fig 8 Pulizia della caldaia 1 Coperchio della mantellatura 2 Piastra di chiusura della camera fumi 3 Scovolo 5 Isolante Smontaggi...

Страница 7: ...e del gas al bruciatore principale Caldaia sporca Controllare e pulire il corpo della caldaia Bruciatore sporco Controllare e pulire il bruciatore Il bruciatore princi pale brucia male Errata regolazi...

Страница 8: ...2 Pn Rendimento Pmax 80 60 C 90 9 91 7 90 9 90 9 Rendimento 30 91 3 91 3 91 5 91 6 Classe efficienza Direttiva 92 42 CE Classe di emissione NOx 2 2 2 2 NOx Ugelli bruciatore G20 n x 2x2 80 3x2 80 3x2...

Страница 9: ...O FRA I MORSETTI 7 e 8 16 Ventilatore 23 Termocoppia 32 Circolatore riscaldamento non fornito 44 Valvola gas 49 Termostato di sicurezza 63 Termostato di regolazione caldaia 72 Termostato ambiente non...

Страница 10: ...Garanzia La presente garanzia convenzionale valida per gli apparecchi Z d K d D E s Z E Z E Y d s FERROLI S p A Via Ritonda 78 a 37047 San Bonifacio Verona Italy tel 39 045 6139411 fax 39 045 6100933...

Страница 11: ...acuerdo con las normas vigentes Las im genes contenidas en este manual son una representaci n simplificada del producto Dicha representaci n puede tener diferencias ligeras y no significativas con res...

Страница 12: ...Cuando se instale la caldera se ha dejar el espacio suficiente a su alrededor para poder efectuar correctamente el mantenimiento 3 3 Conexiones hidr ulicas Advertencias La potencia t rmica del equipo...

Страница 13: ...a la manipulaci n del aparato por personas no autorizadas Regulaci n de la presi n del gas en los quemadores Las calderas PEGASUS 23 T 32 T 35 T 45 T pueden funcionar con gas natural o gas l quido La...

Страница 14: ...n OFF Para un apagado prolongado de la caldera Ponga el interruptor general ref 2 fig 1 en la posici n OFF Mantenga presionado el mando 1 en la posici n C fig 2 Cierre la llave del gas situada antes...

Страница 15: ...a parte posterior de la c mara de humos fig 8 Limpieza de la caldera 1 Tapa de la cubierta 2 Placa de cierre de la c mara de humos 3 Escobilla 5 Aislante Desmontaje y limpieza de los quemadores Para q...

Страница 16: ...olar la presi n del gas en el quemador principal Caldera sucia Controlar y limpiar el cuerpo de la caldera Quemador sucio Controlar y limpiar el quemador El quemador princi pal no quema bien Regulaci...

Страница 17: ...13 0 13 0 17 2 Pn Rendimiento Pm x 80 60 C 90 9 91 7 90 9 90 9 Rendimiento 30 91 3 91 3 91 5 91 6 Clase de eficiencia Directiva 92 42 CE Clase de emisi n NOx 2 2 2 2 NOx Inyectores quemador G20 n x 2...

Страница 18: ...BORNES 7 Y 8 16 Ventilador 23 Termopar 32 Circulador calefacci n no suministrado 44 V lvula del gas 49 Termostato de seguridad 63 Termostato de regulaci n caldera 72 Termostato de ambiente no suminis...

Страница 19: ...A S L U F RROLI ESPA A S L U durante el per odo de garant a durante el per odo de garant a Si el montaje no respeta las instrucciones que se suministran en la m quina Si el montaje no respeta las inst...

Страница 20: ...zetim alt nda olmalar ko uluyla yap labilir phe durumunda cihaz kullanmay n z ve de sa lay c ya d n n z Ayg t n ve buna ait aksesuarlar n imhas d zg n ekilde y r rl kteki standartlara uygun olarak ger...

Страница 21: ...nda yeteri kadar bo luk b rak n z 3 3 Su ba lant lar Uyar lar Cihaz n termik kapasitesi y r rl kteki y netmeliklere g re bina ev s gereksinimi he sab yap larak nceden belirlenmelidir Kombinin d zg n a...

Страница 22: ...unmayan ki ilerin cihaza m dahale etmesinden dolay ortaya kan zarar ve fiziksel yaralanmalardan retici irket sorumlu de ildir Brul r gaz bas nc n n ayarlanmas PEGASUS 23 T 32 T 35 T 45 T kombiler do a...

Страница 23: ...muna getirmek yeterlidir Kombiyi uzun s reli ine kapatmak i in Ana alteri ref 2 ek 1 OFF konumuna getirin Kumanda d mesini 1 bas p evirmek suretiyle C ek 2 konumuna getirin Kombi giri indeki gaz muslu...

Страница 24: ...odas n n arka k sm na monte edilmi olan du man termostat haznesine zarar vermemeye dikkat ediniz ek 8 Kombinin temizlenmesi 1 Muhafaza kapa 2 Duman odas rt plakas 3 F r a 5 Yal t m malzemesi Br l r t...

Страница 25: ...p sk rme Gaz yok Ana br l rdeki gaz bas nc n kontrol edin Kombi kirli Kombinin g vdesini kontrol edin ve temizleyin Br l r kirli Br l r kontrol edin ve temizleyin Ana br l r d zg n yanm yor Alev ayar...

Страница 26: ...0 13 0 17 2 Pn Verim Pmax 80 60 C 90 9 91 7 90 9 90 9 Verim 30 91 3 91 3 91 5 91 6 92 42 CE Direktifi verim s n f NOx Emisyon s n f 2 2 2 2 NOx Br l r u lar G20 n x 2x2 80 3x2 80 3x2 90 4x2 80 Beslem...

Страница 27: ...NDAK K PR Y IKARIN 16 Fan 23 Is l ift 32 Is tma sirk lat r r nle birlikte verilmez 44 Gaz valf 49 Emniyet termostat 63 Kombi ayarlama termostat 72 Oda termostat cihazla birlikte verilmez 98 Sivi 126 D...

Страница 28: ...in compliance with current regulations The images given in this manual are a simplified representation of the product In this representation there may be slight and insignificant differences with resp...

Страница 29: ...ce ac tivities 3 3 Plumbing connections Important The heating capacity of the unit must be previously established by calculating the build ing s heat requirement according to the current regulations T...

Страница 30: ...and unauthorised persons tampering with the unit Adjusting the burner gas pressure The PEGASUS 23 T 32 T 35 T 45 T boilers are arranged to run on natural or liquefied gas Pressure setting and testing...

Страница 31: ...main switch ref 2 fig 1 to OFF Press and turn the control knob 1 to position C fig 2 Close the gas cock ahead of the boiler Disconnect the power to the unit B To avoid damage caused by freezing durin...

Страница 32: ...ons take care not to damage the fume thermostat bulb fitted on the back of the smoke chamber fig 8 Cleaning the boiler 1 Casing cover 2 Smoke chamber closing plate 3 Flue brush 5 Insulation Burner ass...

Страница 33: ...losions at main burner No gas Check the main burner gas pressure Boiler dirty Check and clean the boiler shell Burner dirty Check and clean the burner The main burner burns poorly Incorrect flame adju...

Страница 34: ...2 Pn Efficiency Pmax 80 60 C 90 9 91 7 90 9 90 9 Efficiency 30 91 3 91 3 91 5 91 6 Efficiency class Directive 92 42 EEC NOx emissions class 2 2 2 2 NOx Burner nozzles G20 n x 2x2 80 3x2 80 3x2 90 4x2...

Страница 35: ...NNECT ING THE ROOM THERMOSTAT 16 Fan 23 Thermocouple 32 Heating circulating pump not supplied 44 Gas valve 49 Safety thermostat 63 Boiler control thermostat 72 Room thermostat not supplied 98 Switch 1...

Страница 36: ...er l appareil et s adresser au fournisseur Mettre l appareil et ses accessoires au rebut conform ment aux normes en vigueur Les images contenues dans cette notice ne sont qu une repr sentation simplif...

Страница 37: ...ient de lib rer autour de celle ci l espace n cessaire pour les op rations d entretien et de maintenance pr vues 3 3 Raccordements hydrauliques Avertissements La capacit thermique de l appareil sera p...

Страница 38: ...Les chaudi res PEGASUS 23 T 32 T 35 T 45 T sont r alis es de sorte pouvoir fonctionner au gaz naturel ou au gaz liquide Le test et le tarage de la pression se font en usine Lors du premier allumage e...

Страница 39: ...fig 1 sur OFF Appuyer sur le bouton de commande 1 et le tourner sur la position C fig 2 Fermer le robinet des gaz en amont de la chaudi re D brancher le courant de l appareil B Pour les arr ts prolon...

Страница 40: ...ri re de la chambre des fum es fig 8 Nettoyage de la chaudi re 1 Couvercle du manteau 2 Plaque de fermeture de la chambre de fum es 3 couvillon 5 Isolation D montage et nettoyage du groupe des br leur...

Страница 41: ...n de gaz Contr ler la pression du gaz au br leur principal Chaudi re encrass e Contr ler et nettoyer le corps de chaudi re Br leur sale Contr ler et nettoyer le br leur Le br leur principal fonctionne...

Страница 42: ...0 17 2 Pn Rendement Pmaxi 80 60 C 90 9 91 7 90 9 90 9 Rendement 30 91 3 91 3 91 5 91 6 Classe de rendement selon la directive europ enne 92 42 CE Classe d mission NOx 2 2 2 2 NOx Gicleurs br leur G20...

Страница 43: ...ES BORNES 7 et 8 16 Ventilateur 23 Couple thermo lectrique 32 Circulateur de chauffage non fourni 44 Vanne gaz 49 Thermostat de s curit 63 Thermostat r glage chaudi re 72 Thermostat d ambiance non fou...

Страница 44: ...cod 3541E581 Rev 03 10 2019 UK 1 I i i i i 8 8 i i i i i 2 2 1 PEGASUS 23 T 32 T 35 T 45 T FERROLI i i PEGASUS 23 T 32 T 35 T 45 T 2 2 1 1 i 2 3 4 2 3 4 1 3 2 1 A D 2 15 20 30 1 B 2 4 1 50 A 2 0 30 6...

Страница 45: ...C 2 B 2 4 4 1 30 90 45 i 4 1 1 1 1 0 2 5 i i sez 4 3 i i i 2 6 A i i i i i i i 3 3 1 i B i 3 2 i i i i i i i i i i i i i i i i i i i 3 3 i i i i i i i 20 C B i i i i 13 B i i 25 Fr i i i i i 1 1 5 2 3...

Страница 46: ...i i i i i i i i i Y i i i i i i 3 i 3 i i i 2 B i i i i i i i i i HAR H05 VV F 3x0 75 2 8 A B 3 3 6 i i i i i 4 4 1 i i i i PEGASUS 23 T 32 T 35 T 45 T i i 5 3 1 2 OUT 4 2 3 2 2 1 2 2 2 5 3 2 3 G20 G...

Страница 47: ...2019 4 2 B i i i i i i i i i i i i i i i i i i i i i 2 1 ON sez 2 3 4 1 50 C B 15 i i on page 49 A cap 5 2 1 OFF i 2 1 OFF 1 C 2 B 4 3 i B i i i i i i i i i i i i i i i i 10 1 sez 5 3 i i i i PEGASUS...

Страница 48: ...T 35 T 45 T 48 UK cod 3541E581 Rev 03 10 2019 i 8 7 5 i i i i i i i i i i i i i i i i i i 8 1 2 3 5 i i 1 2 1 2 3 3 4 4 5 i i i i i i i i i i i i 9 10 1 3 i 4 5 6 i 7 8 i 1 5 2 3 3 4 1 2 5 1 6 4 7 8...

Страница 49: ...PEGASUS 23 T 32 T 35 T 45 T 49 UK cod 3541E581 Rev 03 10 2019 4 4 5 I I I 5 1 11 12 10 i i 2 i i i 850 A 615 D...

Страница 50: ...8 8 13 0 13 0 17 2 Pn i i i Pmax 80 60 C 90 9 91 7 90 9 90 9 30 91 3 91 3 91 5 91 6 92 42 CE NOx 2 2 2 2 NOx G20 n x 2x2 80 3x2 80 3x2 90 4x2 80 G20 mbar 20 20 20 20 G20 mbar 15 13 12 15 G20 mbar 2 5...

Страница 51: ...Rev 03 10 2019 5 5 i 16 17 B 7 8 16 23 32 i 44 49 63 72 i 98 126 L 1 2 230V 50Hz N 3 4 5 6 4 16 15 10 11 9 13 14 C 2 1 2 C 7 8 12 44 98 63 126 32 72 49 C 2 23 L N C 1 1 2 3 4 L N 4 5 6 7 8 9 10 11 12...

Страница 52: ...LAS DIRECTIVAS APLICABLES LA DECLARACI N DE CONFORMIDAD PUEDE SOLICITARSE AL FABRICANTE 7bARET7 R NLER7N Y R RL KTE OLAN Y NETMEL7KLER7N TEMEL GEREKL7L7KLER7NE UYGUN OLDU UNU BELGELEMEKTED7R UYGUNLUK...

Страница 53: ......

Страница 54: ......

Страница 55: ...0 32 0 45 0 8 8 13 0 17 2 80 60 90 9 91 7 90 9 30 91 3 91 5 91 6 92 42 CE 2 2 2 G20 2x2 80 3x2 80 4x2 80 G20 20 20 20 G20 15 13 15 G20 2 5 2 5 2 5 G20 3 2 68 3 69 5 24 G20 3 1 07 1 58 2 08 G31 2x1 75...

Страница 56: ...1 03 09 2019 AR 5 5 1 11 12 13 1 5 2 14 22 44 126 156 273 275 A D E F a1 a2 a4 a5 PEGASUS 23 T 400 70 109 112 1 1 2 1 1 2 130 1 2 PEGASUS 32 T 500 70 116 119 1 1 2 1 1 2 130 1 2 PEGASUS 45 T 500 80 73...

Страница 57: ...PEGASUS 23 T 32 T 45 T 8 3541E581 03 09 2019 AR 4 4 10 2 10 2019...

Страница 58: ...PEGASUS 23 T 32 T 45 T 7 3541E581 03 09 2019 AR 10 1 3 4 5 6 7 8 10 2019...

Страница 59: ...PEGASUS 23 T 32 T 45 T 6 3541E581 03 09 2019 AR 7 7 B 8 7 5 8 1 2 3 5 1 2 1 2 3 3 4 4 5 9 10 2019...

Страница 60: ...PEGASUS 23 T 32 T 45 T 5 3541E581 03 09 2019 AR 6 B C 1 2 6 4 2 B 2 1 ON 2 3 4 1 50 B 15 8 A 5 2 1 OFF 2 1 OFF 1 C 2 B 4 3 B 10 1 5 3 PEGASUS 23 T 32 T 45 T 110 10 2 6 B 10 2019...

Страница 61: ...ASUS 23 T 32 T 45 T 4 3541E581 03 09 2019 AR 3 5 B Y 3 3 2 B HAR H05 VV F 3x0 75 2 8 A B 3 3 6 4 4 1 PEGASUS23T 32T 45T 5 3 1 2 OUT 4 2 3 2 2 1 2 2 2 5 3 2 3 G20 G25 G30 G31 1 2 4 A 5 5 3 4 5 4 5 10 2...

Страница 62: ...PEGASUS 23 T 32 T 45 T 3 3541E581 03 09 2019 AR 1 C 2 B 2 4 4 1 30 90 45 4 1 1 1 1 0 2 5 4 3 2 6 A 3 3 1 B 3 2 3 3 20 B 13 B 25 1 1 5 2 3 4 B 13 B 3 1 10 2019...

Страница 63: ...PEGASUS 23 T 32 T 45 T 2 3541E581 03 09 2019 AR AR 1 8 8 2 2 1 PEGASUS 23 T 32 T 45 T FERROLI PEGASUS 23 T 32 T 45 T 2 2 1 1 2 3 4 2 3 4 1 3 2 1 A D 2 15 20 30 1 B 2 4 1 50 A 2 CE 10 2019...

Страница 64: ...3541E581 10 2019 03 PEGASUS 23 T 32 T 45 T...

Отзывы: