11
TECHNICAL DATA AND PERFORMANCES
NOMINAL performances - Radiant plants
NOMINAL performances - Standard plants
Data declared according to
EN 14511 .
The values are referred to units without options or accessories.
Data declared according to
EN 14511 .
The values are referred to units without options or accessories.
IP
Heating A7W35
( source : air in 7°C d.b. 6°C w.b. / plant : water in 30°C out 35°C )
Heating capacity
4,76
5,83
6,92
8,03
10,2
11,9
15,7
18,6
kW
Power input
1,21
1,49
1,87
2,28
2,86
3,39
4,28
5,29
kW
COP
3,93
3,91
3,70
3,52
3,57
3,51
3,67
3,52
-
Water flow rate plant side
823
1008
1195
1385
1749
2043
2702
3204
l/h
Pressure drops plant side
10
15
20
25
37
47
51
46
kPa
Heating A2W35
( source : air in 2°C d.b. 1°C w.b. / plant : water in 30°C out 35°C )
Heating capacity
3,95
4,85
5,75
6,67
8,43
9,85
13,1
15,5
kW
Power input
1,19
1,47
1,84
2,24
2,81
3,31
4,17
5,16
kW
COP
3,32
3,30
3,13
2,98
3,00
2,98
3,14
3,00
-
Water flow rate plant side
684
838
994
1152
1453
1697
2251
2667
l/h
Pressure drops plant side
7
11
14
18
27
35
38
34
kPa
Cooling A35W18
( source : air in 35°C d.b. / plant : water in 23°C out 18°C )
Cooling capacity
5,12
6,27
7,43
8,60
10,8
12,6
16,7
19,8
kW
Power input
1,54
1,91
2,39
2,91
3,64
4,32
5,44
6,73
kW
EER
3,32
3,28
3,11
2,96
2,97
2,92
3,07
2,94
-
Water flow rate plant side
885
1085
1286
1490
1879
2190
2914
3448
l/h
Pressure drops plant side
12
17
22
28
41
53
58
52
kPa
IP
Heating A7W45
( source : air in 7°C d.b. 6°C w.b. / plant : water in 40°C out 45°C )
Heating capacity
4,65
5,70
6,76
7,84
9,91
11,6
15,3
18,2
kW
Power input
1,44
1,78
2,23
2,72
3,40
4,02
5,06
6,27
kW
COP
3,23
3,20
3,03
2,88
2,91
2,89
3,02
2,90
-
Water flow rate plant side
806
989
1171
1357
1712
1999
2642
3146
l/h
Pressure drops plant side
10
14
19
24
35
45
49
45
kPa
Heating A2W45
( source : air in 2°C d.b. 1°C w.b. / plant : water in 40°C out 45°C )
Heating capacity
3,84
4,72
5,59
6,49
8,19
9,58
12,7
15,1
kW
Power input
1,42
1,76
2,20
2,68
3,34
3,95
4,96
6,15
kW
COP
2,70
2,68
2,54
2,42
2,45
2,43
2,56
2,46
-
Water flow rate plant side
667
819
970
1124
1418
1656
2190
2607
l/h
Pressure drops plant side
7
10
14
18
26
33
36
33
kPa
Cooling A35W7
( source : air in 35°C d.b. / plant : water in 12°C out 7°C )
Cooling capacity
4,24
5,20
6,15
7,14
8,98
10,4
13,9
16,5
kW
Power input
1,50
1,85
2,31
2,80
3,50
4,14
5,21
6,46
kW
EER
2,83
2,81
2,66
2,55
2,57
2,51
2,67
2,55
-
Water flow rate plant side
729
894
1059
1229
1548
1802
2403
2849
l/h
Pressure drops plant side
8
12
16
21
30
39
42
38
kPa
Frame
1
2
3
Model
5 .1
6 .1
7 .1
8 .1
10 .1
12 .1
15 .1
18 .1
U.M.
Power supply
230 -1- 50
230 -1- 50
230 -1- 50
230 -1- 50
230 -1- 50
400 -3N- 50
230 -1- 50
400 -3N- 50
400 -3N- 50
400 -3N- 50
V-ph-Hz
Frame
1
2
3
Model
5 .1
6 .1
7 .1
8 .1
10 .1
12 .1
15 .1
18 .1
U.M.
Power supply
230 -1- 50
230 -1- 50
230 -1- 50
230 -1- 50
230 -1- 50
400 -3N- 50
230 -1- 50
400 -3N- 50
400 -3N- 50
400 -3N- 50
V-ph-Hz