For the use of a further heat source (e.g. solid fuel boiler),
one or two thermostat functions can be activated additional-
ly to the differential function, in order to allocate a minimum
temperature to the boiler or to limit the maximum store
temperature.
In order to control a circulation pump, it might be enough
to activate the timer. With the aid of the 3 time frames,
the
relay can be switched individually in the morning, at noon
and in the evening. This process can be further optimised by
activating a thermostat function so that - with a sensor in the
circulation line- control is also temperature-dependent.
S3
R3
arrangement/Options/
D
T-Func6
...........change setting to “Yes“
arrangement/Options/Thermo.3
...........change setting to “Yes“
arrangement/adj. values/t-Th3 on
.....change value to “60“
arrangement/adj. values/t-Th3 off
....change value to“55“
arrangement/Options/Thermo.4
...........change setting to “Yes“
arrangement/adj. values/t-Th4 on
.....change value to “58“
arrangement/adj. values/t-Th4 off
...change value to “60“
minimum temperature limitation for the boiler
maximum temperature limitation for the store
arrangement/Options/timer 1
........................................................change setting to “Yes“
arrangement/adj. values/timer 1/t1 on
.......................................change value to “06:00“
arrangement/adj. values/timer 1/t1 off
.....................................change value to“08:00“
arrangement/adj. values/timer 1/t2 on
......................................change value to“11:30“
arrangement/adj. values/timer 1/t2 off
....................................change value to “13:30“
arrangement/adj. values/timer 1/t3 on
......................................change value to “18:00“
arrangement/adj. values/timer 1/t3 off
....................................change value to “21:00“
arrangement/Options/Thermo. 1
...................................................change setting to “Yes“
arrangement/adj. values/t-Th1 on
...............................................change value to“50“
Aarrangement/adj. values/t-Th1 off
...........................................change value to “55“
S5
S6
R6
D
T6-S5>S6
Th3-S5
Th4-S6
R6
Th1-S3
Timer 1
R3