ATLAS D 34 CONDENS K130 UNIT
40
EN
cod. 3541Q644 - Rev. 01 - 11/2022
System water pressure adjustment
The filling pressure with system cold, read on the display, must be approx. 1.0 bar. If the
system pressure falls to values below minimum, the boiler card will activate fault F37
(fig. 15).
fig. 15 - Low system pressure fault
Filling cock kit
The boiler is provided with a kit comprising a filling cock.
The cock must be installed respecting the direction of the arrow.
When installed, operate the filling cock (detail 1 - fig. 16) to bring the system pressure to
a value above 1.0 bar.
fig. 16 - Filling cock
A
Once the system pressure is restored, the boiler will activate the 120-second
air venting cycle indicated on the display by FH.
3. INSTALLATION
3.1 General Instructions
BOILER INSTALLATION MUST ONLY BE PERFORMED BY QUALIFIED PERSON-
NEL, IN ACCORDANCE WITH ALL THE INSTRUCTIONS GIVEN IN THIS TECHNICAL
MANUAL, THE PROVISIONS OF CURRENT LAW, THE PRESCRIPTIONS OF NA-
TIONAL AND LOCAL STANDARDS AND THE RULES OF PROPER WORKMANSHIP.
3.2 Place of installation
The boiler unit must be installed in a specific room with ventilation openings to the out-
side as prescribed by current regulations. If there are several burners or suction units
that can work together in the same room, the ventilation openings must be sized for si-
multaneous operation of all the units. The place of installation must be free of flammable
materials or objects, corrosive gases, powders or volatile substances that, conveyed by
the burner fan, can obstruct the internal lines of the burner or the combustion head. The
room must be dry and not exposed to rain, snow or frost.
A
If the unit is enclosed in a cabinet or mounted alongside, a space must be pro-
vided for removing the casing and for normal maintenance operations.
3.3 Plumbing connections
Important
The heating capacity of the unit must be previously established by calculating the build-
ing's heat requirement according to the current regulations. The system must be provid-
ed with all the components for correct and regular operation. It is advisable to install
shutoff valves between the boiler and heating system allowing the boiler to be isolated
from the system if necessary.
B
The safety valve outlet must be connected to a funnel or
collection pipe to prevent water spurting onto the floor in
case of overpressure in the heating circuit. Otherwise, if
the discharge valve cuts in and floods the room, the boiler
manufacturer cannot be held liable.
Do not use the water system pipes to earth electrical ap-
pliances.
Before installation, flush all the pipes of the system thoroughly to remove any residuals
or impurities that could affect proper operation of the unit.
Carry out the relevant connections according to the diagram in cap. 5 and the symbols
given on the unit.
B
Install the safety check valve (supplied with the boiler) on
the cold water inlet.
High efficiency hot water tank circulating pump
For proper operation of the boiler ATLAS D 34 CONDENS K130 UNIT, the speed selec-
tor (see fig. 17) must be set to position III.
fig. 17
High efficiency heating circulating pump
The factory setting is suitable for all installations; however a different operation strategy
can be set, depending on the characteristics of the system.
- Proportional Head Dp-v setting
(fig. 18)
The circulating pump head will be automatically reduced with the decrease in flow rate
required by the system. This setting is optimum for systems with radiators (2 pipes or sin-
gle pipe) and/or thermostatic valves.
The strong points are the reduction in power consumption with the decrease in system
demand and reduction of noise in radiators and/or thermostatic valves. The operating
range is from min. (1) to max. (7).
- Setting Fixed speed
(fig. 19)
The circulating pump does not modulate its power. The operating principle is that of con-
ventional 3-speed circulating pumps (with a reduction in power consumption compared
to them). The operating range goes from speed 1 (I) to speed 3 (III).
1
Setting
Dp-v
Proportional head
fig. 18
Setting
Fixed speed
fig. 19
Min
.
4
1
7
III
II
I
Min
.
4
1
7
III
II
I
Min
.
4
1
7
III
II
I