GAS VALVE ADJUSTMENT
Maximum rate adjustment
Switch the boiler on and operate for 10 minutes.
To ensure the boiler operates at maximum rate without modulating
follow the instruction on page 19.
Insert the Flue Gas Analyser (FGA) probe into the test point.
Remove the plastic cover from the gas valve to gain access to the
adjustment screw.
Using a 4mm Allen key adjust as necessary to achieve the correct
CO
2
reading shown in the table below. (Clockwise to decrease, anti-
clockwise to increase)
Minimum rate adjustment
.
Adjust the modulation rate to minimum (0%) as described on page 19
Allow combustion and flame to stabilise then compare CO
2
reading to
that given in the table below.
To adjust, remove adjustment cover with a flat blade screwdriver.
Using a 40Torx driver adjust CO
2
(Clockwise to increase, anti-
clockwise to decrease) to that given in the table below.
Replace covers.
Emissions Values
CO
2
NO
x
CO
CO/CO
2
Minimum
9%
< 39 ppm
<100 ppm
<0.004
Maximum
9.50%
< 39 ppm
<100 ppm
<0.004