BLUEHELIX PRIMA 24 C
26
EN
cod. 3541R820EN - Rev. 03 - 03/2020
Notes:
1. The Maximum Power parameter can also be modified in Test Mode.
Press the Reset button to return to the Service Menu. Press the Reset button for 10 seconds to exit the card Service
Menu, or exiting occurs automatically after 15 minutes.
P41
Max. output in heating
0 ÷ 85%
80
P42
Burner shutdown in DHW
0
=Fixed
1
=Linked to setpoint
2
=Solar
0
P43
Comfort activation temperature
0 ÷ 80°C
40
P44
Comfort deactivation hysteresis
0 ÷ 20°C
20
P45
DHW standby time
30 ÷ 255 seconds
120
P46
DHW user max. setpoint
40 ÷ 65°C
55
P47
DHW pump Post-Circulation
0 ÷ 255 seconds
30
P48
Max. output in DHW
0 ÷ 100%
100
P49
Not implemented (b01=2)
--
--
P50
Not implemented (b01=2)
--
--
P51
Solar off temperature
0 ÷ 100°C
10
P52
Solar on temperature
0 ÷ 100°C
10
P53
Solar standby time
0 ÷ 255 seconds
10
P54
System pre-circulation time
0 ÷ 60 seconds
30
P55
System filling mode
0
= Disabled
1
=Automatic
0
P56
Minimum system pressure limit value
0-8 bar/10 (Only for boilers with water pressure sensor)
4
P57
System nominal pressure value
5-20 bar/10 (Only for boilers with water pressure sensor)
7
P58
Maximum system pressure limit value
25-35 bar/10 (Only for boilers with water pressure sensor)
28
P59
Not implemented
--
--
P60
Frost protection power
0 ÷ 50% (0 = minimum)
0
P61
Minimum power
0 ÷ 50% (0 = minimum)
0
P62
Fan minimum speed
Modify only when using Ø50 and Ø60 flues (see table 8 and )
76
P63
Fan on speed
200
P64
Fan maximum speed
204
Contents
Description
Range
Default