Variable output relay card LC32 (optional - 043011X0)
The variable output relay
LC32
consists of a small card with a switchover of free contacts (closed means contact bet-
ween C and NO). Operation is managed by the software.
For installation, carefully follow the instructions provided in the kit package and on the wiring diagram of fig. 55.
To use the desired function, refer to the table 2.
Table 2- Settings LC32
ON/OFF (A fig. 19) configuration
Table 3- Switch A setting
2.6 Fume ducts
B
THE BOILER MUST BE INSTALLED IN PLACES THAT MEET THE FUNDA-
MENTAL REQUIREMENTS FOR VENTILATION. OTHERWISE THERE IS A
DANGER OF SUFFOCATION OR INTOXICATION.
READ THE INSTALLATION AND MAINTENANCE INSTRUCTIONS BEFORE
INSTALLING THE UNIT.
ALSO FOLLOW THE DESIGN INSTRUCTIONS
.
IN CASE OF PRESSURES ABOVE 200 Pa INSIDE THE FUME EXHAUST PI-
PES, CLASS "H1” FLUES MUST BE USED.
Important
The unit is a “C type” with sealed chamber and forced draught; the air inlet and fume outlet must be connected to one
of the extraction/suction systems indicated below. Before proceeding with installation, check and carefully observe the
above instructions. Also, comply with the provisions on the positioning of wall and/or roof terminals and the minimum
distances from windows, walls, ventilation openings, etc.
In case of installation with maximum resistance (coaxial or separate chimney) it is advisable to perform a com-
plete manual calibration to optimize boiler combustion
.
Parameter b07
Function LC32
Action LC32
0
Manages a secondary gas valve (default)
The contacts are closed when the gas valve (in the boiler) is
powered
1
Use as an alarm output (warning light comes on)
The contacts are closed when there is an error condition (generic)
2
Manages a water loading valve
The contacts are closed until the water pressure in the heating cir-
cuit is restored to the normal level (after manual or automatic top-
ping up)
3
Manages a solar 3-way valve
The contacts are closed when the DHW mode is active
4
Manages a second heating pump
The contacts are closed when the heating mode is active
5
Use as an alarm output (warning light goes off)
The contacts are opened when there is an error condition (gene-
ric)
6
Indicates ignition of the burner
The contacts are closed when the flame is present
7
Manages the trap heater
The contacts are closed when the frost protection mode is active
DHW configuration
Parameter b06
b01 = 3
b06=0
Contact open disables DHW and re-enables it if closed.
b06=1
Contact open disables heating and displays
F50
. Contact closed enables heating.
b06=2
The contact acts as a room thermostat.
b06=3
Contact open displays
F51
and the boiler continues to operate.
It is used as an alarm.
b06=4
The contact acts as a limit thermostat, if open it displays
F53
and turns off the request.